DETAILED PARAMETER DESCRIPTION
Table 5.28:
Forward/Reverse Selection LOCAL Situation
Function
0
Always forward
1
Always reverse
2
HMI
key (Forward default)
3
HMI
key (Reverse default)
4
Digital Input DI2 (P0264 = 0)
5
Serial (Forward default)
6
Serial (Reverse default)
7
Fieldbus (Forward default)
8
Fieldbus (Reverse default)
9
AI4 Polarity
10
Forward PLC
11
Reverse PLC
12
Graphic HMI
key (Forward)
13
Graphic HMI
key (Reverse)
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0224 - Start/Stop Selection LOCAL Situation
Adjustable range:
0 to 5
Factory setting:
5
Acesso:
Menu
→
Configurations
→
Commands
→
Local
Description:
It defines the origin of the Start/Stop command in the LOCAL situation.
When the DIx inputs have the FORWARD/REVERSE function, the HMI keys
|
and
O
will remain inactive
regardless of the value set in P0224 (Start/Stop Selection LOCAL Situation).
Table 5.29:
Start/Stop Selection LOCAL Situation
Function
0
HMI
l
and
0
keys
1
Digital input DIx
2
Serial
3
Fieldbus
4
PLC
5
Graphic HMI
|
and
O
key
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0225 - Selection of JOG Source LOCAL Situation
Adjustable range:
0 to 6
Factory setting:
6
Acesso:
Menu
→
Configurations
→
Commands
→
Local
Description:
It defines the origin of the JOG command in the LOCAL situation.
MVW3000 | 5-37