5
DETAILED PARAMETER DESCRIPTION
P1553 - Transformers rated voltage
Adjustable range:
0.00 to 99.99 kV
Factory setting:
6.60 kV
Acesso:
Menu
→
Configurations
→
Nominal data
→
Inverter
Description:
It sets the rated line voltage of the input transformer, in kV effective value.
Set it according to the nameplate data of the transformer used.
✓
NOTE!
This parameter can be changed only with the motor stopped.
P1554 - Transformer 1 rated power
Adjustable range:
0 to 10000 kVA
Factory setting:
1500 kVA
Acesso:
Menu
→
Configurations
→
Nominal data
→
Inverter
Description:
It sets the rated power of the input transformer, in kVA.
Set it according to the nameplate data of the transformer used.
✓
NOTE!
This parameter can be changed only with the motor stopped.
P1555 - Transformers rated frequency
Adjustable range:
0 to 100 Hz
Factory setting:
60 Hz
Acesso:
Menu
→
Configurations
→
Nominal data
→
Inverter
Description:
It sets the rated frequency of the input transformer, in Hertz (Hz).
Set it according to the nameplate data of the transformer used.
✓
NOTE!
This parameter can be changed only with the motor stopped.
P1556 - Transformer 2 CT Ratio
Adjustable range:
50 to 3000
Factory setting:
200
Acesso:
Menu
→
Configurations
→
Nominal data
→
Inverter
Description:
It sets the ratio of the current transformers used in the measurement of the inverter input current.
Set it according to the current transformer nameplate data.
Notes:
It is recommended that the CT primary current be greater than or equal to the transformer primary rated current.