General Information
MOD1...MOD7 | 2-3
2
2.4 MODELS
2.4.1 MOD1.yz
MOD1.00 - 24DIs: model with 24 digital inputs.
MOD1.10 - 24DOs: model with 24 digital outputs.
MOD1.20 - 08DO/16DI: model with 8 digital outputs and 16 digital inputs.
MOD1.30 - 16DO/8DI: model with 16 digital outputs and 8 digital inputs.
All digital inputs are bidirectional, isolated and must be activated by a 24 V power supply.
All digital outputs are isolated, protected and PNP type (they activate the load connected to the common or V- of
the power supply), voltage level of 24 Vdc, and they can supply a maximum current of 500 mA each.
2.4.2 MOD2.yz
MOD2.00 - 7AIs: model with 7 analog voltage or current inputs.
For analog inputs configured in voltage measurement mode, it is possible to measure voltages between 0 and 10 V.
For inputs configured in current measurement mode, it is possible to measure currents in the range 0…20 mA,
with configuration for sensors from 4mA to 20mA.
2.4.3 MOD3.yz
MOD3.00 - 8 AOs (V) / 4 AOs (I): model with 8 analog outputs. 4 of them in voltage and current and 4 only in
voltage.
Voltage outputs can generate voltages from 0 to 10 V. Current outputs can provide currents between 0 and 20
mA for a maximum load of 500 Ω.
2.4.4 MOD4.yz
MOD4.00 - 7 TH: model with 7 inputs for type J, type K and type T thermocouples.
2.4.5 MOD5.yz
MOD5.00 - 4 PT100 / 4 PT1000: model with input for up to 4 temperature sensors of PT100 or PT1000 type.
It is possible to connect to the MOD5.00 PT100/PT1000 sensors with 2 and 3 wires.
2.4.6 MOD6.yz
MOD6.00 - 2 SG: model with input for up to two load cells.
It is possible to connect to the MOD6.00 4 and 6-wire load cells.
2.4.7 MOD7.yz
MOD7.yz - 6 RE: model with 6 relay outputs.
All relay outputs are isolated and designed to work with maximum currents of 8 A and voltages up to 250 V.