5-4 | CFW-11M RB
First Time Power-Up and Start-Up
The use of the Oriented Start-up routine for setting the converter parameters may lead to the automatic
modification of other internal parameters and/or variables of the converter.
During the Oriented Start-up routine, the message “Config” will be displayed at the left top corner of the
keypad.
Step
Action/Result
Display Indication
Step
Action/Result
Display Indication
1
- Monitoring Mode.
- Press
“Menu”
(right soft key).
Ready
RB + LOC
618V
13:48
Menu
0
A
618
V
380
V
2
- Group
“00
ALL PARAMETERS”
is
already selected.
Ready
RB + LOC
618V
Return
13:48 Selec.
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
3
- Group
“01 PARAMETER
GROUPS”
is selected.
Ready
RB + LOC
618V
Return
13:48 Selec.
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
4
- Group
“02 ORIENTED
START-UP”
is then
selected.
- Press
“Select”
.
Ready
RB + LOC
618V
Return
13:48 Selec.
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
5
- Parameter
“Oriented
Start-Up P0317: No”
is
already selected.
- Press
“Select”
.
Ready
RB + LOC
618V
Return
13:48
Selec.
Oriented Start-Up
P0317: No
6
- The value of
“P0317 = [000] No”
is
displayed.
Ready
RB + LOC
618V
Return
13:48
Save
P0317
Oriented Start-up
[000] No
7
- The parameter value is
modified to
“P0317 =
[001] Yes”.
- Press
“Save”
.
Ready
RB + LOC
618V
Return
13:48
Save
P0317
Oriented Start-up
[001] Yes
8
- At this point the Oriented
Start-up routine starts
and the “Config” status
is displayed at the top left
corner of the keypad.
- The parameter
“Language P0201:
English”
is already
selected.
- If needed, change the
language by pressing
“Select”
. Then, press
or
to scroll through the
available options and
press
“Save”
to select a
different language.
Config RB + LOC
618V
Reset
13:48 Selec.
Language
P0201: English
DI1 Function
P0263: General Enable
9
- If needed, change the
value of P0263 according
to the application. To do so,
press
“Select”
.
- It is necessary to have one
DI set to General Enable
in order the regenerative
converter can be enabled.
Config RB + LOC
618V
Reset
13:48 Selec.
DI1 Function
P0263: General Enable
Line Rated Voltage
P0296: 440 - 460V
10
- If needed, change the
value of P0296 according
to the line voltage. To do
so, press
“Selec.”
. This
change will affect P0151.
Config RB + LOC
618V
Reset
13:48 Selec.
DI1 Function
P0263: General Enable
Line Rated Voltage
P0296: 440 - 460 V
11
- If needed, change the
value of P0298 according
to the application. To do
so, press
“Select”
. The
time and the activation
level of the IGBT’s overload
protection will be affected
as well.
- To complete the Oriented
Start-Up routine, press
“Reset”
(left soft key).
Config RB + LOC
618V
Reset
13:48
Selec.
Line Rated Voltage
P0296: 440 - 460V
Switching Frequency
P0297: 2.5 kHz
Config RB + LOC
618V
Reset
13:48 Selec.
Switching Frequency
P0297: 2.5 kHz
Application
P0298: Normal Duty (ND)
12
- After few seconds, the
display returns to the
Monitoring Mode.
Ready
RB + LOC
618V
13:48
Menu
0
A
618
V
380
V
Figure 5.2 -
Oriented Start-up