LX3V-2TC2DAI-BD

 

1                                                       

                                                                             

WECON Technology Co., Ltd. 

1.

 

Installation Instructions 

 

Before installation, it is necessary to ensure that the associated equipment of the PLC host and the 

terminal of the BD module are reliably powered off. 

 

This  module  comes  with  two  standard  terminals;  please  plug  the  terminals  into  the  module 

terminals  after  wiring.  Confirm  the  installation  of  host,  module  and  wiring  are  correct  and  then 

power on. 

 

 

Caution

 

1)

 

When  using  current  output,  make  sure  that  the  external  load  resistance  is  ≤500Ω.  If  the 

external load resistance> 500Ω, the output current will be lower than normal; 

2)

 

To  install  the  function  expansion  board  firmly  and  fix  it  on  the  PLC,  poor  contact  may  cause 

malfunction; 

3)

 

The fastening torque is 0.3-0.6N.m. Firmly screw down to prevent malfunctions; 

4)

 

The PLC main  unit of the LX3V can only use one BD  board. Don’t try to use two  or more BD 

boards (these BD boards will not work); 

5)

 

When mounting module to PLC, all the lights are blinking after power ON PLC, it means this PLC 

can’t support it, please purchase new PLC. 

 

Warnings

 

Cut  off  the  electricity  before  installation/disassembly  of  the  unit  or  connection  of  wires  onto  the 

unit, to prevent electric shock or product damage. 

 

2.

 

Features of LX3V-2TC2DAI-BD 

 

1)

 

It could use LX3V-2TC2DAI-BD to add  2 analog input  points and 2 current  output points. It is 

internally  installed  in  the  top  of  PLC,  thus  it  is  not  necessary  to  change  the  PLC’s  installation 

area. 

2)

 

The analog digital conversion of LX3V-2TC2DAI-BD module is thermocouple input (K or J type), 

current output (4~20mA), and the data of all the channels after conversion are stored inside a 

special digital memory, but the converted characteristics of the analog data cannot be adjusted. 

The allocation of the relevant channel addresses is in the following table. 

 

Summary of Contents for LX3V-2TC2DAI-BD

Page 1: ...LX3V 2TC2DAI BD User manual Website http www we con com cn en Technical Support support we con com cn Skype fcwkkj Phone 86 591 87868869 QQ 1043098682 Technical forum http wecon freeforums net...

Page 2: ...it of the LX3V can only use one BD board Don t try to use two or more BD boards these BD boards will not work 5 When mounting module to PLC all the lights are blinking after power ON PLC it means this...

Page 3: ...communicating PLC OFF when timeout CH1 LED LED for CH1 constantly ON when analog signal in range lit when analog signal out of range K type 100 1200 J type 100 600 M8112 OFF K type M8112 ON J type CH2...

Page 4: ...0 70mA Powered by PLC host Temperature input TC Analog input signal Thermocouple K or J type 2 channels CH1 CH2 Range of rated temperature K 100 1200 J 100 600 Digital output K 1000 12000 J 1000 6000...

Page 5: ...e cable shall be grounded But their grounding point can be the same with high voltage lines 3 Never connect cable with forbidden size 4 Fix the cable so that the stress does not act on the terminal bo...

Page 6: ...e cable stripped jacket Then connect the cable AWG16 1 309 5 2 Input and output mode 1 Thermocouple input mode 2 Current Output Mode 6 Example The analog values of each channel are transfer to digital...

Page 7: ...er counter 6 2 Application example Since the LX3V 2TC2DAI BD does not have offset and gain functions if it needs for the values out of the standard specifications Additional programming orders will be...

Page 8: ...mula Fahrenheit Celsius 9 5 32 the unit is 0 1 2 Current output mode In current output mode it changes the digital value 0 2000 to analog value 4 20mA If the real digital range is 0 A A means any valu...