LX3V-2TC2DAI-BD

 

4                                                       

                                                                             

WECON Technology Co., Ltd. 

 

Insulation   

No insulation in each PLC channel 

Occupied points 

None 

   

Note: 

This module does not support grounding thermocouples. 

 

5.

 

Wire Connection 

 

Warning:   

Make  sure  cut  off  the  electricity  before  installation/disassembly,  to  prevent  electric  shock  or 

product damages. 

 

Caution:   

1)

 

Please keep the signal cable from the high-voltage cable at lease 100mm.

 

2)

 

The  shielding  wire  cable  shall  be  grounded.  But  their  grounding  point  can  be  the  same  with 

high-voltage lines. 

3)

 

Never connect cable with forbidden size. 

4)

 

Fix  the  cable,  so  that  the  stress  does  not  act  on  the  terminal  board  or  the  cable  connection 

area. 

5)

 

The screwing torque of the terminal is from 0.5 to 0.6N.m. Fasten tight to prevent malfunction. 

6)

 

Keep the redundant terminals empty. 

 

5.1 Applicable Cables 

Use AWG25-16 to connect the output equipment 

The maximal screwing torque is from 0.5 to 0.6N.m 

The use of different types of cables might cause poor contact between the terminals. It is better to 

use pressed terminals. 

Summary of Contents for LX3V-2TC2DAI-BD

Page 1: ...LX3V 2TC2DAI BD User manual Website http www we con com cn en Technical Support support we con com cn Skype fcwkkj Phone 86 591 87868869 QQ 1043098682 Technical forum http wecon freeforums net...

Page 2: ...it of the LX3V can only use one BD board Don t try to use two or more BD boards these BD boards will not work 5 When mounting module to PLC all the lights are blinking after power ON PLC it means this...

Page 3: ...communicating PLC OFF when timeout CH1 LED LED for CH1 constantly ON when analog signal in range lit when analog signal out of range K type 100 1200 J type 100 600 M8112 OFF K type M8112 ON J type CH2...

Page 4: ...0 70mA Powered by PLC host Temperature input TC Analog input signal Thermocouple K or J type 2 channels CH1 CH2 Range of rated temperature K 100 1200 J 100 600 Digital output K 1000 12000 J 1000 6000...

Page 5: ...e cable shall be grounded But their grounding point can be the same with high voltage lines 3 Never connect cable with forbidden size 4 Fix the cable so that the stress does not act on the terminal bo...

Page 6: ...e cable stripped jacket Then connect the cable AWG16 1 309 5 2 Input and output mode 1 Thermocouple input mode 2 Current Output Mode 6 Example The analog values of each channel are transfer to digital...

Page 7: ...er counter 6 2 Application example Since the LX3V 2TC2DAI BD does not have offset and gain functions if it needs for the values out of the standard specifications Additional programming orders will be...

Page 8: ...mula Fahrenheit Celsius 9 5 32 the unit is 0 1 2 Current output mode In current output mode it changes the digital value 0 2000 to analog value 4 20mA If the real digital range is 0 A A means any valu...