Wecon LX3V-2ADV-BD User Manual Download Page 4

                                                                                                                                       

LX3V-2ADV-BD

 

3                                                       

                                                                           

  WECON Technology Co., Ltd. 

4.

 

Specification 

1)

 

Please refer to the LX3V user manual for the general specification of LX3V-2ADV-BD. 

2)

 

LX3V-2ADV-BD is powered supply by LX3V main unit. 

Table 4-1 

Item 

Specification 

Voltage input 

Input range 

DC -10 ~ 10V    (Input resistance:150KΩ) 

Digital output   

12 bits binary 

Resolution   

4mV (10 : 1/2000) 

Precision   

±1% 

AD conversion time  One PLC scanning cycle 

Characteristic   

 

Insulation   

No insulation in each PLC channel 

Occupied points 

None 

 

5.

 

Wiring 

Caution:   

1)

 

Don’t  put  the  LX3V-2ADV-BD  module  near  high-voltage  power  cable.  Keep  away  the  power 

cable at least 100mm; 

2)

 

Do not solder any terminal with the others device; 

3)

 

Do not connect any unsuitable cable; 

4)

 

Please fix cable; 

5)

 

Do not connect any unit to the unused terminal; 

 

5.1 Suitable cable   

Connect to output device with AWG25-16. 