LX3V-2ADV-BD
1
WECON Technology Co., Ltd.
1.
Mounting instruction
Before the installation make sure that the PLC host and the equipment connected to BD module
have been powered off. Please install the BD module in the corresponding position of the PLC, and
lock the two standard screws.
Caution:
1)
This BD module only support the following firmware versions or later. Users can check the PLC
firmware version in D8001.
LX3VP:25103;
LX3VE: 25201;
LX3V-A2:25014;
LX3V-A1: 22006;
When mounting module to PLC, all the lights are blinking after power ON PLC please purchase a
new PLC.
2)
Please fixed BD module on the PLC, poor contact may lead to failure.
3)
BD module and top cover of PLC’s tightening torque is 0.3 ~ 0.6 N.m.
Warning:
Make sure to power off the PLC before mounting or removing the BD module and put the cover in
right place.
2.
Special feature
1)
LX3V-2ADV-BD module equips with 2 channels analog input. This module will be mounted in
the PLC.
2)
The input voltage of LX3V-2ADV-BD module between -10 to 10V, and the digital value will be
saved in special system address, but the numerical relationship between input and output value
cannot be changed.
Table 2-1
Expansion port 1 (far away from PLC light )
Address
Description
M8112
The flag of switching input mode in CH1
OFF: Voltage input mode (-10V~10V, -2000~2000)
ON:
Disabled