LX3V-2ADV-BD
User manual
Website:
http://www.we-con.com.cn/en
Technical Support:
[email protected]
Skype:
fcwkkj
Phone:
86-591-87868869
QQ:
1043098682
Technical forum:
http://wecon.freeforums.net/
Page 1: ...LX3V 2ADV BD User manual Website http www we con com cn en Technical Support support we con com cn Skype fcwkkj Phone 86 591 87868869 QQ 1043098682 Technical forum http wecon freeforums net...
Page 2: ...e a new PLC 2 Please fixed BD module on the PLC poor contact may lead to failure 3 BD module and top cover of PLC s tightening torque is 0 3 0 6 N m Warning Make sure to power off the PLC before mount...
Page 3: ...10V 10V 2000 2000 D8117 The digital value of channel 2 10V 10V 2000 2000 3 Dimension Table 3 1 LED lights indicating 1 LED1 ON when power ON 2 LED2 flashes when communications 3 LED3 AD 1 On indicate...
Page 4: ...ary Resolution 4mV 10 1 2000 Precision 1 AD conversion time One PLC scanning cycle Characteristic Insulation No insulation in each PLC channel Occupied points None 5 Wiring Caution 1 Don t put the LX3...
Page 5: ...e form of data Values will be automatically stored when the END order is sent out The value is calculated by the designated analog data conversion characteristics of the special auxiliary relays M8112...
Page 6: ...e Under the voltage input mode the 2ADV will convert the analog value 10V 10V into data output 2000 2000 If the data range used in the application is 0 20000 then the range 2000 2000 must be converted...
Page 7: ...LX3V 2ADV BD 6 WECON Technology Co Ltd the situation of CH1 Version V1 0 1 Date Feb 2018...