3 Functional Description
Thermo 90
304
3.6.3 Diagnosis after Switch-off upon Failure
(Thermo 90 S)
When equipped with a standard timer an error will cause
an output to the timer display:
F 01
No start (after 2 start attempts)
F 02
Flame-out during operation (repeated > 5)
F 03
Voltage too low or too high
F 04
Premature flame detection
F 05
Flame sensor open or short circuit
F 06
Temperature sensor open or short circuit
F 07
Dosing pump open or short circuit
F 08
Fan motor open or short circuit or wrong speed
of fan motor
F 09
Glow plug open or short circuit
F 10
Overheating
F 11
Circulation pump open or short circuit
When operated with switch the type of error lock-out
condition is indicated by an operation indicator light flash
code while the heater is in run-down.
After five short signals the following long flash pulses are
counted:
1x
No start (after 2 start attempts)
2x
Flame-out during operation (repeated > 5)
3x
Voltage too low or too high
4x
Premature flame detection
5x
Flame sensor open or short circuit
6x
Temperature sensor open or short circuit
7x
Dosing pump open or short circuit
8x
Fan motor open or short circuit or wrong speed of
fan motor
9x
Glow plug open or short circuit
10x
Overheating
11x
Circulation pump open or short circuit
Summary of Contents for Thermo 90
Page 9: ...1 Introduction 104 Page free for notes ...
Page 13: ...2 General Description Thermo 90 204 Page free for notes ...
Page 18: ...Thermo 90 3 Functional Description 305 Page free for notes ...
Page 20: ...4 Technical Data Thermo 90 402 Page free for notes ...
Page 26: ...6 Functional Tests Thermo 90 602 Page free for notes ...
Page 41: ...Thermo 90 8 Servicing 809 Page free for notes ...
Page 53: ...10 Packaging Storage and Shipping Thermo 90 1002 Page free for notes ...