Code 

Description 

Possible 

Default 
Recommended 

Chiller 

CPAC  AirH. 

Set security CODE. 

00 = No access code 
required. Possible to 
set at 01 - 99. 
If security code is set 
active, only the 
temperature set point 
and blower speed 
settings can be 
changed. 

  64 Chiller / 
CPAC 
  00 Air handler 

● 

● 

● 

Dehumidifying heating 
run time. 

Min. 1 / Max. 99 
minutes 
Recommended:  
Chiller 40 in winter 
and 15 in summer 
times. 
CPAC 30 in winter and 
10 in summer times. 
Set 45 in tropical 
conditions with hot 
sea-water. 

  01 CPAC  / 
Air handler  

● 

● 

● 

Dehumidifying cooling 
run time. 

Min. 01 / Max. 99 
minutes 
Recommended: 
Chiller 20 in winter 
and 45 in summer 
times. 
CPAC 15 in winter and 
30 in summer times. 
Set 1 in tropical 
conditions with hot 
sea-water. 

  01 CPAC / Air 
handler 

● 

● 

● 

 

 

Summary of Contents for Azimut 43 Fly

Page 1: ...ogramming RETURN Push 1x display will return to room temperature during FUNCTION mode programming FUNCTION Push 1x shows b for blower setting Push 2x shows E or H for evaporator temp Push 3x shows CODE entering code will give access to programming mode level 2 Default 64 Change b or enter CODE by pushing up or down key after 5 seconds new settings will be auto memorized UP Push 1x will show actual...

Page 2: ... temperature E10 5 Evaporator temperature Actual temperature Actual temperature F Cycle mode 01 Cooling only 02 Heating only by reverse cycle 03 Automatic cooling or heating by reverse cycle 04 Automatic cooling or heating by external heater 03 CPAC CHILLER 01 Air handler Never set F2 or F3 without reversing valve mounted 05 Heating only with external heater 01 Solenoid valve only 02 Solenoid valv...

Page 3: ...Thermostati c advance comp 4 4L0 0 4 C 0 C 4 C switching off comp 4 0 0 d Automatic dehumidifyi ng when unit is switched off 1 0 not active 1 1x in 24h 2 2x in 24h 3 3x in 24h 00 1 To synchronize clock air handler and chiller controller cut off the main supply after setting a dehumidifying cycle and controllers are shut off See also settings c and d in 15 C menu Don t set d1 d3 when onboard or it ...

Page 4: ...to stage multiple units with independent controllers Min 01 Max 20 seconds 01 Chiller CPAC 05 Air handler 7 Calibration room temperature sensor Min 9 9 Max 9 9 C 0 0 8 Calibration AC Voltage 50Hz Min 20 Max 20 Hz 00 9 Setting relay R2 Chiller 00 Staging relay 01 Air handler 3 way valve controlling 02 Alarm indication 03 Cycle indication 00 Chiller Air handler De icing CPAC 00 99 minutes anti short...

Page 5: ...not change 01 CPAC Air handler 3 Blower control 00 Blower speed regulated 01 Blower speed uninterrupted 00 Chiller Air handler 01 CPAC 4 Internal external room temp sensor 00 External room temperature sensor 01 Internal room temperature sensor 00 Chiller 01 CPAC Air handler 5 Display in Fahrenheit or Celsius 00 Celsius 01 Fahrenheit Changing F C will change all settings into F or C 00 6 Setting fa...

Page 6: ... 00 Air handler c Dehumidifying heating run time Min 1 Max 99 minutes Recommended Chiller 40 in winter and 15 in summer times CPAC 30 in winter and 10 in summer times Set 45 in tropical conditions with hot sea water 01 CPAC Air handler d Dehumidifying cooling run time Min 01 Max 99 minutes Recommended Chiller 20 in winter and 45 in summer times CPAC 15 in winter and 30 in summer times Set 1 in tro...

Page 7: ...All contacts from both compressor relays and capacitors ...

Page 8: ...Bleed Valve ...

Page 9: ......

Page 10: ...Carefully apply upward pressure to compressor Cut old mount ...

Page 11: ... New Compressor Spacer PPC301010A Anti Vibration Plate ...