15˚C Menu
Code
Description
Possible
Default
Recommended
Chiller
CPAC AirH.
0
Low AC voltage cut-out Min.160 / Max.210
Volt
Starting surge voltage
drops are not taken
into account.
After 90 seconds a
restart will be
attempted.
Settings below 195 V
will void
WARRANTY!
195
Chiller/CPAC
●
●
1
Infrared remote-control.
00 = Not active 01 =
Active.
00
●
●
●
2
Setting Relay R1.
00 = Cycle indication
T1=Heat / R1=Cool
cycle.
01 = Alarm indication
T1=system block /
R1= OK.
00 Chiller
●
Blower type.
00 = centrifugal
blowers only 01 = All
types of blowers.
Avoid blower
burn-out, do not
change!
01 CPAC / Air
handler
●
●
3
Blower control.
00 = Blower speed
regulated.
01 = Blower speed
uninterrupted.
00 Chiller / Air
handler
01 CPAC
●
●
●
4
Internal / external room
temp sensor.
00 = External room
temperature sensor.
01 = Internal room
temperature sensor.
00 Chiller
01 CPAC / Air
handler
●
●
●
5
Display in Fahrenheit or
Celsius.
00 = Celsius.
01 = Fahrenheit.
Changing F/ ˚C will
change all settings
into F or ˚C.
00
●
●
●
6
Setting fan speed level
5 (high).
Min. 18 / Max. 70
Ensure blower start-
up.
70
●
●
●
7
Setting fan speed level
4.
Min. 18 / Max. 70
Ensure blower start-
up.
40
●
●
●
8
Setting fan speed level
3.
Min. 18 / Max. 70
Ensure blower start-
up.
35
●
●
●
9
Setting fan speed level
2.
Min. 18 / Max. 70
Ensure blower start-
up.
29
●
●
●
A
Setting fan speed level
1 (low).
Min. 18 / Max. 70
Ensure blower start-
up.
23
●
●
●