Brine Fogging System Type SOLFOG V3
Index: 02
Change date: 19/09/2023
OI No.: BA DW 042-02 Solfog V3 CB36 EN.docx
Page 22 of 65
6
Electrical installation
6.1
Safety notices
WARNING!
Danger of electric shock!
Dangerous electrical voltage!
All work on the device must be carried out by specialist personnel only!
All electrical installations and any work on the device’s electrical components
must be carried out by authorised electricians only!
Prior to starting work, disconnect the devices from the power supply and se-
cure them against being reactivated!
After corresponding electrical installation or repair, test all protective
measures used (e.g., earthing resistance)!
6.2
Electrical connection
1)
For additional equipotential bonding, an earthing connection (page 12, pos. 11) is provided
on the mounting plate.
2)
Connect the SOLFOG to the power supply (110-230 V AC, 50/60 Hz) with the power plug.
6.3
Additional connection options
The following additional connection options exist:
NOTICE
Electric wiring: See wiring diagram in Chapter 11.2 on page 60.
Description
Bar
Terminals
Collective fault to CCS (Central Control System)
SL 4
1/2/3
Operating contact with a potential-free signal
When the operating contact is open, the device is in standby
position (e.g., during downtimes)
When the operating contact is closed, the device is ready for
operation (e.g., during operation times)
SL 13
4/5
External control (e.g., via central control or BCS)
The device can be activated (fog on) or deactivated (standby
position) via the external contact.
As long as the contact is closed, fog is produced.
The contact is only active when the “EXTERNAL” operation
mode is selected.
The dosing time and pause time can be specified with an ex-
ternal control unit.
SL 10
4/5