Operation manual Soldos - SL (04-09) page 10 of 18
6.2 Operation modes
The programme switch is to set the demanded programme. There are 2
general operation modes:
6.2.1 Interval operation - „continuous dosing“
At the continuous dosing the programme starts after the unit has been
switched-on. The spraying time is adjustable by a rotary knob on 5-10-
15-20-25-30-35 or 40 seconds. The pause time between the single
sprays is adjustable on 1-2-3-4-6-8-10 or 12 minutes. This cycle is
repeated until the unit is switched-off.
Put the programme switch on „continuous dosing“. The LED „continuous
dosing“ shines. Adjust now the spraying- and the pause time.
Example: pause time 4 minutes, spraying time 20 seconds
The unit sprays brine solution every 4 minutes for 20 seconds.
6.2.2 Push-button operation
The push-button has to be connected according to the wiring diagram.
The demanded cycle time is adjusted at the programme switch. The LED
“push-button operation” shines.
After pressing the connected push-button the same procedure as described
above (“continuous dosing”) starts. After the lapse of the adjusted cycle
time on 5 – 10 – 15 – 20 or 25 minutes the dosing stopps and the
SOLDOS is ready for a restart.