![Wayne Reliance G6101D Installation & Operation Manual Download Page 13](http://html1.mh-extra.com/html/wayne/reliance-g6101d/reliance-g6101d_installation-and-operation-manual_3948334013.webp)
920943 Rev E July 2014
9
Union-Top Emergency
Shear Valves must be
used due to height
restrictions.
1-1/2" Supply
Line
(If Solenoid Valve
has pressure relief,
separate relief
valve is not needed.)
Shelf
Bracket
Model G6101D
Dispenser
Electrical
Conduit
1-1/2" Union-Top
Emergency
Shear Valve
Relief Valve
Expansion
Submersible
Pump
Gate Valve
(Block Valve)
(Anti-Siphon)
Solenoid Valve
3 INSTALLATION
3.1 Equipment
Inspection
Examine the shipment immediately upon arrival to make certain there has been no damage
or loss in transit. Make sure that all the component parts, including keys and any optional
equipment, are accounted for.
Check and save the Packing Slip, Bill of Lading, Invoice, and all other documents included in
the shipment.
Damaged or lost equipment must be reported to the carrier. Any damage or loss that may
occur in transit is not covered under the Wayne Warranty.
Explosive or flammable vapors may accumulate within the dispenser housing. All piping
connections in the final installation must be accurately fitted and all threaded joints tightly made up
with a Listed gasoline-resistant pipe joint compound. Put the compound on male threads only,
being careful not to get excess inside the pipe or fittings. Failure to perform the above will present
a hazardous condition that could result in serious injury.
3.2
Typical Site Layouts
Figure 3-1 Submersible Site Layout
WARNING
Summary of Contents for Reliance G6101D
Page 8: ...4 920943 Rev E July 2014...
Page 20: ...16 920943 Rev E July 2014...
Page 24: ...20 920943 Rev E July 2014...
Page 32: ...28 920943 Rev E July 2014...
Page 33: ...920749 Rev G 7 2014 29 APPENDIX A DIMENSIONS BASE LAYOUTS...
Page 36: ...32 920749 Rev G 7 2014 Rotate Upwards 26 301 4 Hose Mast Dimensions...
Page 40: ...36 920749 Rev G 7 2014...