DIRECT SPARK IGNITION SINGLE ROD TROUBLESHOOTING INFORMATION
NOTE 1: BURNERS ARE NOT PRESET FROM THE FACTORY AND MUST BE ADJUSTED AT THE SITE.
NOTE 2: NEW GAS LINE INSTALLATIONS WILL HAVE AIR IN THE LINES AND REQUIRE SEVERAL IGNITION ATTEMPTS
TO PURGE ALL THE AIR FROM THE LINES.
NOTE 3: DO NOT ATTEMPT TO PERFORM ANY WORK ON THIS BURNER UNLESS THE FOLLOWING TOOLS ARE
AVAILABLE AND YOU ARE A CERTIFIED INSTALLER:
I . VOLT METER-VOLTS, OHMS, CONTINUITY
2. AMP METER-CLAMP TYPE
3. BURNER MANUAL
4. MANOMETER
5. BLADE SCREW DRIVERS
6. NUT DRIVERS
7. OPEN END WRENCHS
8. TAPE MEASURE
The Wayne Burner that you are attempting to troubleshoot has the following electrical 115 Volt Single phase components:
1. 115 volt Combustion Fan Motor w/End Switch
2. Fan Relay-24 volt coil side and 110 volt fan side
3. Honeywell Gas primary Control(24 VOLT)
4. Honeywell Gas Valve(24 VOLT)
5. 24 volt Transformer
6. Ignition Rod/Sensing Rod
7. Ignition Lead
8. T-T (24 VOLT) TERMINAL