Initial start-up 

Initial start-up is needed to verify whether the dispenser is in perfect operating condition. 
Before starting the dispenser, ensure that all installation procedures have been properly carried out (hydraulic 
connections, sealing of the fittings, electrical connections, etc.). 
Make sure that the junction boxes are properly closed and that all cable glands are accurately fastened.  
The  junction  boxes  must  not  present  any  signs  of openings; any holes not intended for the cables must be 
closed with original plugs. 
 
The first start-up of the CNG dispenser must be performed by properly trained personnel. To install the CNG 
dispenser, follow the procedure below: 

 

 

Switch dispensing selector to the OFF position; 

 

Power the dispenser complying with the values listed on the corresponding electrical schemes; 

 

Switch dispensing selector to the ON position; 

 

Place  the  hydraulic  circuit  under  pressure  and  ensure  there  are  no  leaks  on  the  hydraulic 
connections; 

 

Switch the dispensing selector to the OFF position; 

 

Clean  the  dispenser  (minimum  delivery  of  10  m

3

  of  gas)  by  dispensing  some  gas  following  the 

procedure indicated in the following paragraph; 

 

Check the meter’s calibration by dispensing gas a few times and comparing the measurements 
given  by  the  electronic  head  with  those  given  by  a  proper  sampling  instrument  (For  Example: 
precision scale); 

 

Dispensing procedure 

To dispense CNG, follow these procedures: 

 

remove the nozzle from its housing; 

 

connect  the  nozzle  to  the  vehicle’s  tank  or  to  a  test  tank  (suitable  for storing natural gas at the 
maximum fuelling pressure); 

 

bring the three-way valve to the «ON» position (dispensing); 

 

start dispensing by activating the dispensing selector switch (bring it to the «ON» position); 

 

the dispenser manages the end of delivery and the stop appears when a pre establish value of 
pressure or low flow is reached; 

 

after stop switch the dispensing selector to the «OFF» position; 

 

bring the three-way valve to the «VENT»  position (no dispensing); 

 

remove the nozzle from the vehicle’s tank or from the test tank; 

 

re-insert the nozzle in its housing; 

 

 

 

 

Note 1: the three-way valve can be integrated onto the nozzle or separated. 
Note  2:  a  light  signal  always  indicates  the  operating  status  of  the  dispenser  (green=  dispenser 
ready; red= dispenser fuelling or in error) 
Note 3: Pay attention to activate the selector switch only after the three way valve is ON position. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for GLOBAL VISTA CNG

Page 1: ...EN WT004139 2008 03 20 V0 Rev 01 0 Global Vista CNG Instruction Manual ...

Page 2: ...ния перед началом любых работ Warning Never run a leaking pump Be careful with the environ ment and mind the skidding risk take care of leaking fuel immediately Varning Använd aldrig en läckande pump Tänk på miljön och halk risken sanera utläckt driv medel snarast Warnung Lassen Sie nie eine undichte Zapfsäule laufen Seien Sie umweltbewusst und denken Sie an die Rutschgefahr beseitigen Sie austret...

Page 3: ...stallation 9 Initial start up 16 Dispensing procedure 16 COMPONENTS 17 Hydraulic components 17 Electrical components 17 HYDRAULIC COMPONENTS 18 Manual ball valve 18 Particulate filter 18 Check valve 18 Mass flow meter 18 Motorized valve 18 Pressure gauge 18 Delivery hose 18 Delivery Nozzle 18 Three way valve 19 Breakaway Device 19 ELECTRICAL COMPONENTS 19 Electronic head 19 Electrical components u...

Page 4: ...Dresser will not be held responsible for any tampering performed by the customer who in this case will be the only party held liable by the competent authorities For further information on the main components of the equipment mass flow meter actuator board etc and or original spare parts see the specific technical documentation given to your technical assistance after sales company Warnings for fu...

Page 5: ... positions of these warnings depend on local conditions but they must be visible from the dispenser Ensure that all station attendants know how to behave in an emergency situation Protection from pressure related risks The hydraulic circuit of the dispenser works under pressure Before performing any maintenance accurately close the cut off valve s located at the base of the dispenser and release t...

Page 6: ...e prohibit or restrict access to the switches used to interrupt power supply to the dispenser Ensure that the fuelling station has both an electrical line equipped with an automatic breakaway device as well as a proper grounding system in compliance with all applicable regulations Dispenser Identification The GLOBAL VISTA CNG dispenser can be manufactured in different versions due mainly to the di...

Page 7: ...the mass flow meter in the dispenser The information given by the mass flow meter or any other sensors temperature sensor pressure sensor etc are processed by the electronic head which carries out specific operations based on the values it receives The CNG dispensers can be Single stage dispensers that control a single valve first stage level their hydraulic system communicates with one storage ta...

Page 8: ...the areas indicated with the arrows in this diagram areas are about 50 cm one from the other Always use the proper methods to lift and transport the dispenser Non compliance with the instructions for moving the dispenser could cause serious damages to things and people Once you have received the dispenser carefully inspect the equipment to ensure that it has not been damaged during transportation ...

Page 9: ...tem normally composed of an emergency button and one or more safety switches that is capable of interrupt the flow to the equipment in case of operating problems The emergency stopping system not included with the dispenser must comply with national regulations for example EN 60204 1 The safety device must be placed in the gas station in order that it is easily accessible to attendants Following a...

Page 10: ... Copyright 2008 03 20 V0 Rev 01 0 10 WT004139 ...

Page 11: ... Copyright 2008 03 20 V0 Rev 01 0 11 WT004139 ...

Page 12: ... Copyright 2008 03 20 V0 Rev 01 0 12 WT004139 ...

Page 13: ... Copyright 2008 03 20 V0 Rev 01 0 13 WT004139 ...

Page 14: ... Copyright 2008 03 20 V0 Rev 01 0 14 WT004139 ...

Page 15: ... Copyright 2008 03 20 V0 Rev 01 0 15 WT004139 ...

Page 16: ... by dispensing some gas following the procedure indicated in the following paragraph Check the meter s calibration by dispensing gas a few times and comparing the measurements given by the electronic head with those given by a proper sampling instrument For Example precision scale Dispensing procedure To dispense CNG follow these procedures remove the nozzle from its housing connect the nozzle to ...

Page 17: ... and electrical components External components 1 Lower front panel 2 Column 3 Nozzle Housing 4 Computing Head Housing 5 Cover 6 Base 7 Id plate Hydraulic components 8 Manual ball valve 9 Particulate filter 10 Check valve 11 Mass flow meter 12 Motorized valve 13 Pressure gauge 14 Delivery hose 15 Delivery Nozzle 16 Breakaway Device Electrical components 17 Electronic head 18 Pressure transmitter 19...

Page 18: ...he motorized valve includes a ball valve a solenoid and a pneumatic actuator When the dispensing selector is switched to the ON position dispensing the head sends a command to the solenoid which activates the inlet of compressed air into the actuator through the inlet door at this point the ball valve opens and the gas starts to flow The motorized valve returns to its initial position when the hea...

Page 19: ...damages to persons the dispenser and the vehicle ELECTRICAL COMPONENTS Electronic head Description The CNG dispenser is equipped with a Dresser electronic head which guarantees high performance in calculating and constantly monitoring all the operations carried out by the dispenser The head designed specifically to manage CNG dispensers performs the following operations management and control of t...

Page 20: ...NTENANCE The dispenser leaves the factory only after passing accurate tests hydraulic and electrical A correct installation and use should guarantee proper functioning In any case in order to maintain the dispenser s optimal conditions in time and guarantee its safety the station manager must check the components listed in the table below periodically Component Intervention Pneumatic actuator Peri...

Page 21: ... remember to disconnect the power supply before operating on the components of the CNG dispenser Cleaning To clean the dispenser do not use abrasive detergents or products petrol petroleum based products Instead use water with non aggressive detergents and soft cloths Adopt all necessary precautions to avoid any water entering the dispenser Before entering the head box carefully dry any traces of ...

Page 22: ...ens while the volume display will show the pre established unit price for example 1 235 0 1 235 1 235 For example pressing P0 once and P1 twice the display will appear as follows 2 1 235 Pressing P0 again another digit is added on the display and it can be increased or decreased by pressing P1 or P2 respectively 20 1 235 The same applies when setting the next digits If the new price is set the dat...

Page 23: ...an be set with the P001 parameter Values are 0 e 1 0 manual mode 1 automatic mode Warning if the dispenser is connected to the Host it will shift into automatic mode even if it is set to manual Further information For further information regarding programming operation and the meaning of certain error codes displayed by the electronic head refer to the related manual ...

Page 24: ... Year of construction 3 Type of product 4 Space for directions 5 II 3 G group II surface category 3 potentially explosive atmosphere due to presence of gas vapors or fog 6 CE marking in compliance with EMC and ATEX 7 Epsilon X marking in compliance with the ATEX directive 8 Name and address of the manufacturer 3 1 2 ID PLATE 4 5 6 7 8 ...

Page 25: ... Copyright 2008 03 20 V0 Rev 01 0 25 WT004139 DECLARATION OF CONFORMITY ...

Page 26: ...____________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ ___...

Page 27: ...V0 Rev 01 0 27 WT004139 MARKET SERVICE To obtain name and address of the closest authorized maintenance company please contact DRESSER WAYNE DRESSER Italia S r l Via Roma 32 23018 TALAMONA SO Tel 0342 608111 Fax 0342 608299 ...

Page 28: ...n with overall responsibility to the customer Field service technical support and supply of spare parts Ausrüstungen wie Zapfsäulen Zahlterminals Kassenterminals und Tankstellensysteme Software für Registrierung und Kommunikation auf der Tankstelle u zwischen Station und Mineralölfirma sowie Banken und Kreditinstituten Projektgestaltung mit umfassender Verantwortlichkeit dem Kunden gegenüber Servi...

Reviews: