INSTALLATION MANUAL

 

6

 

1.  Discharge Ou 

2.  Junction Box 

3.  Pump/Switch 

4.  Union 

5.  Effluent Inlet  

6.  Switches 

tlet Pipe 

7. Septic Tank 

8. Effluent Pump 

 Wires 

9. Brick or Block 

10. Discharge Pipe 

Pipe 

11. Check Valve 

12. Tank Lid 

TYPICAL SEWAGE INSTALLATION 

1.  This installation must be in accordance with the 

National Electric Code and all applicable local codes 
and ordinances. 

2.  For sump applications, follow typical sump installation 

instructions (page 3). For effluent applications, follow 
typical effluent installation instructions (page 4). For 
sewege applications, proceed to step 3. 

3.  Use a basin that is large enough to accommodate the 

pump.  The basin diameter should be a minimum of 18 
inches and the depth a minimum of 24 inches. 

4.  Clean the basin of all debris.  

5.  Set the pump on a solid, level surface.  Do not place 

pump directly on clay, earth, gravel, or sand.  A brick or 
block may be installed under the pump to provide a 
solid base. 

6.  Position pump in the basin so the switch is away from 

incoming water.  Verify the float switch has at least 1 
inch clearance to the side wall of the basin and is free 
of any possible obstructions. 

7.  Install discharge plumbing according to local, regional 

and state codes.  Do not reduce the discharge pipe size 
below that which is provided on the pump. 

8. 

If required, drill a 1/8 in. “weep” hole in the discharge 
pipe 1 in. above the pump discharge.  Water stream will 
be visible from this hole when the pump is running.  The 
hole must be cleaned periodically. 

9.  If optional control device or float is used, follow 

mounting instruction supplied with device or float.  

10.  A union should be installed above the basin to allow 

easy removal of the pump for cleaning and service. 

11.  Install a check valve (required) to prevent back-flow. It 

should be installed above the union. 

12.  A gate valve or ball valve should be installed above the 

check valve as required by local, regional or state 
codes. 

13.  Connect remaining discharge pipe.  The remainder of 

the discharge line should be as short as possible with a 
minimum number of turns. 

14.  A vent pipe is required.  It removes gases and odors 

and should be installed as required by local, regional or 
state codes. 

15.  Secure power supply cord to discharge pipe using 

cable or zip ties to prevent possible switch 
entanglement.  

16.  Connect pump power supply cord to a properly 

grounded receptacle. 

17.  Fill the basin with water. The pump will start when the 

water level has reached the switch-on level.  Verify the 
pump is operating normally. 

18.  Install a basin cover and gasket to prevent debris from 

falling into the basin, prevent personal injury and to 
contain gases and odors. 

Summary of Contents for CDU980E

Page 1: ...ING WARNINGS MAKE SURE THERE IS A PROPERLY GROUNDED RECEPTACLE AVAILABLE This pump is supplied with a grounding conductor and grounding type attachment plug To reduce the risk of electric shock be cer...

Page 2: ...A CHECK VALVE with this pump to prevent the back flow of fluid after each pump cycle DO NOT INSTALL OR OPERATE THE PUMP IF IT HAS BEEN DAMAGED IN ANY WAY DO NOT LIFT OR CARRY THE PUMP BY THE POWER COR...

Page 3: ...n 22 in Vertical Float Switch 11 in 22 in CHART B Switch Type A Minimum Basin Diameter B Maximum Basin Height Pedestal Float Switch Figure 2 on page 2 14 in 24 in 3 Clean the basin of all debris 4 Ass...

Page 4: ...le 14 Fill the basin with water The pump will start when the water level has reached the switch on level 15 The pump will stop when the water level has reached the switch off level 16 Verify the switc...

Page 5: ...n the pump is running The hole must be cleaned periodically 9 Install a union to allow easy removal of the pump for cleaning and service 10 Install a check valve required to prevent back flow It shoul...

Page 6: ...the discharge pipe size below that which is provided on the pump 8 If required drill a 1 8 in weep hole in the discharge pipe 1 in above the pump discharge Water stream will be visible from this hole...

Page 7: ...ECT THE PUMP FROM POWER SUPPLY before to water installing servicing or making any adjustments 3 Submersible pump may contain dielectric oil for cooling Dielectric oil can be harmful to the environment...

Page 8: ...etermine cause and then either replace with proper sized fuse or reset breaker 3 Low line voltage 3 Contact an electrician 4 Motor 4 Replace pump 5 Switch 5 Replace switch 6 Inlet screen clogged6 Remo...

Page 9: ...peller cavity 5 Pump not properly sized for application 6 Check valve stuck closed or installed backwards 7 Shut off valve closed 1 Contact an electrician 2 Remove debris 3 Remove screen and volute cl...

Page 10: ...INSTALLATION MANUAL 10 NOTES...

Page 11: ...SUIVRE TOUTES LES INSTRUCTIONS CONSERVER CES INSTRUCTIONS NE PAS LES JETER DIRECTIVES DE S CURIT Ce manuel contient de l information tr s importante conna tre et comprendre Cette information est fourn...

Page 12: ...ST PAS VIT E POURRAIT RISQUER D ENTRA NER DES L SIONS CORPORELLES MINEURES OU MOD R ES POUR R DUIRE LE RISQUE DE DANGERS QUI PEUVENT MENER DES BLESSURES OU DES DOMMAGES LA PROPRI T OBSERVER LES AVERTI...

Page 13: ...VOIR TAB LEA U B COLON NE B 1 SORTIE DU DISJONCTEUR DE 5 TUYAU D ENTR E FUITE LA TERRE 6 TUYAU DE D CHARGE 2 CLAPET DE NON RETOUR 7 POMPE DE PUISARD 3 TUYAU D A RATION 8 INTERRUPTEUR 4 JOINT COUVERCLE...

Page 14: ...est visible du trou lorsque la pompe fonctionne Le trou doit tre nettoy p riodiquement 9 Installer un raccord union pour permettre d enlever facilement la pompe pour le nettoyage ou l entretien 10 Ins...

Page 15: ...u de PVC rigide Cette pompe n est pas con ue pour l eau sal e la saumure l eau de d charge de buanderie les adoucisseurs d eau les eaux us es ou n importe quelle application qui pourraient avoir des p...

Page 16: ...ent 9 Installer un raccord union pour permettre d enlever facilement la pompe pour le nettoyage et l entretien 10 Installer un clapet de non retour requis pour viter tout retour d eau Il doit tre inst...

Page 17: ...MANUEL D INSTALLATION 17 pr venir les blessures personnelles et contenir les gaz et les odeurs...

Page 18: ...d charge de la pompe Le courant d eau est visible du trou lorsque la pompe fonctionne Le trou doit tre nettoy p riodiquement 9 Si un appareil de contr le ou un flotteur optionnel est utilis suivre les...

Page 19: ...s roulements lubrifi s en permanence et n exigent aucune lubrification suppl mentaire 2 La pompe doit tre inspect e 3 4 fois par an pour le mouvement de pompe ou l accumulation de d bris sur l interru...

Page 20: ...1 L eau doit tre au niveau appropri pour activer l interrupteur 2 Si grill d terminer la cause puis remplacer en utilisant la bonne taille de fusible ou r initialiser le disjoncteur 3 Contacter un lec...

Page 21: ...nement de votre pompe de puisard au moins une fois par an D PANNAGE SUITE Sympt mes Cause s possible s Rem des Sugg r s La pompe fonctionne bruyamment ou vibre trop 1 Roulements us s 2 Impulseur obstr...

Page 22: ...rre au besoin S assurer que la pompe elle m me est en position verticale En cas de vibrations pendant son utilisation elle risque de tomber ou de s incliner d un c t Ceci pourrait bloquer le bras du f...

Page 23: ...tas advertencias puede dar como resultado la muerte o lesiones graves y o da os a la propiedad DESCRIPCIONES BOMBAS DE SUMIDERO Las bombas de sumidero son bombas autom ticas usadas para quitar aguas d...

Page 24: ...ulg a 19 1 cm 3 4 pulg de di metro BOMBAS DE AGUAS CLOACALES Las bombas de aguas cloacales son bombas usadas para quitar aguas de desecho que contienen s lidos hasta 5 1 cm 2 pulg de di metro La aplic...

Page 25: ...ANOS DESPU S DEL MANEJO Seg n el estado de California Puntal 65 este producto puede contener productos qu micos conocidos al estado de California por causar c ncer y defectos de nacimiento u otros da...

Page 26: ...NO LAS DESECHE GU AS DE SEGURIDAD Este manual contiene informaci n que es muy importante que se conozca y comprenda Esta informaci n se proporciona con fines de SEGURIDAD y para EVITAR PROBLEMAS CON...

Page 27: ...CCI N DENTRO DE LA PILETA Se recomienda que el instalador pruebe y observe el funcionamiento de la bomba por varios ciclos despu s de la instalaci n NO USE BOMBAS DE SUMIDERO Y BOMBAS DE AGUAS RESIDUA...

Page 28: ...flotador de pedestal Figura 2 p gina 18 35 56 cm 14 pulg 60 96 cm 24 pulg 3 Limpie la pileta de todo residuo 4 De ser necesario ensamble el interruptor o el flotador Refi rase a garant a y servicio ho...

Page 29: ...o o flotador 7 Instale la tuber a de descarga seg n los c digos locales regionales y estatales No reduzca el tama o de la tuber a de descarga por debajo de lo que se proporciona en la bomba 8 Si fuera...

Page 30: ...ara sumideros p gina 19 Para aplicaciones de aguas residuales siga las instrucciones de instalaci n t picas para aguas residuales p gina 20 Para aplicaciones de alcantarillado avance al paso 3 3 Use u...

Page 31: ...c digos locales regionales o estatales 15 Sujete el cable de suministro de energ a a la tuber a de descarga usando un cable o precintos para evitar posibles enredos del interruptor 16 Conecte el cable...

Page 32: ...ltos o bajos un cableado inadecuado condiciones incorrectas del motor o un motor o bomba defectuosos DIAGN STICO Y RESOLUCI N DE PROBLEMAS S ntomas Causa s posible s Remedios sugeridos La bomba no enc...

Page 33: ...place el interruptor 2 Quite la obstrucci n para asegurar el libre movimiento del interruptor 3 Quite la obstrucci n de la tuber a de descarga 4 Vuelva a calcular las dimensiones para determinar el ta...

Page 34: ...sto podr a obstruir el brazo flotador de modo tal que no pudiera activar la bomba ierta un balde de agua en el pozo y aseg rese de que la bomba arranque autom ticamente y el agua se drene r pidamente...

Page 35: ...MANUAL DE INSTALACI N 35...

Reviews: