background image

Wavecom Instruments Portable Appliance Testers Instruction Manual

 

 

 

 

Important Information 

Accessories Supplied 

 

Portable Appliance Tester Instruction Manual

 

 

Manufacturer

’s 1

st

 Calibration Certificate 

– (Valid for 12 months)

 

 

IEC test lead (500mm orange/red)

 

 

Earth Lead with Alligator Clip (1800mm black)

 

 

Soft Carry Case

 

 

Locking IEC Power Cable (1800mm Blue)

 

 

*Battery model (power bank)

 

 

*

Battery model USB lead

 

Precautions  

 

 

Manufacturer Recommendations 

Calibration

:

 The manufacturer recommends a routine calibration / verification of this unit to ensure the accuracy 

of readings on a 12 monthly basis, or as prescribed under any additional local Regulatory requirements.  

Note:

  Only  Wavecom  Instruments  or  its  Authorised  Service  Agents  are  permitted  to  repair  and  Calibrate  this 

Instrument. Failure to perform unauthorised service or repair may void all warranties and Calibration Status.  

TnT  Firmware  &  TnT  G4  series  in  general  have  the  ability  to  be  updated  to  comply  with  potential  Changes  in 
Testing Standards 

Safety Warning   

This  4

th

  Generation  TnT  series  of  products  have  been  designed  to  meet  stringent  safety 

requirements, however no device can completely protect persons from the consequences of incorrect use. 
 
The testing of Electrical appliances requires that extra care and caution is taken  at all times to ensure personal 
safety. 
 
The Manufacturer also advises that appliance testing should be conducted by a 

Competent

 and suitably trained 

person, as referred to under the current Standard AS3760:2010, as well as any additional legislation or rulings in 
different states.  
If in doubt, the manufacturer suggests the user contact their responsible Authority. 

For maximum safety, always ensure that the following advice is followed:

 

 

The equipment being tested is in good repair

 

All user instructions are followed.

  

 

Double check power supply connections. (note LED status)

  

 

Always use specified fuses and protection devices.

  

 

Do not use leads that require repair or are damaged.

  

 

If you are unsure, call a licensed Engineer/Electrician

 

* See P.5 AS/NZ 3760:2010 def. 

Unique Locking Power Cable 

Please make sure yellow lever is pressed prior to removal of 
the  locking  power  supply  cable.  Though  the  case  of  the  G4 
TnT is manufactured from impact resistant & flame retardant 
ABS,  failure  to  do  so,  combined  with  excessive  force  may 
damage the rear panel. 

Switch from battery power to mains power 

To switch from battery power to mains power, simply plug in 
the supplied blue power cord. There is no need to disconnect 
the battery cable. However, it is advised to disconnect the 
USB AM-BM cable from USB B port from the rear of unit. 

In case of switching from mains power to  power bank 
or switching off the unit using Enter button, disconnect 
the USB cable from  USB B port of unit and connect it 
back, press the Enter button to start the unit. 

 

 
 

 

Summary of Contents for TnT ELB G4-Series

Page 1: ...ad Findon SA 5023 Phone 61 08 8243 3500 Fax 61 08 8243 3501 Email sales wavecom com au Web www wavecom com au Melbourne Office 772A Station Street Box Hill Victoria 3128 Phone 1300 793 301 Fax 61 03 9...

Page 2: ...Wavecom Instruments Portable Appliance Testers Instruction Manual 2...

Page 3: ...ure personal safety The Manufacturer also advises that appliance testing should be conducted by a Competent and suitably trained person as referred to under the current Standard AS3760 2010 as well as...

Page 4: ...tery power bank DO NOT send this item by any shipping company This includes the power bank by itself or with equipment Please remove the battery power bank first If you have any transportation queries...

Page 5: ...ipment The knowledge of how to use the relevant testing instruments interpret and record the results for compliance with the Standard Workplace requirements The knowledge to be able to correctly recom...

Page 6: ...method of construction employs two safety barriers comprising two layers of insulation between dangerous voltages and the user of the equipment The first layer of insulation is formed around the live...

Page 7: ...ps MAXIMUM Resistive Load only Standard TNT Series units A Leakage Test applies power to the Device under Test DUT and measures the imbalance of leakage current from the DUT between the active and neu...

Page 8: ...est function ensures that the appliance is plugged into the TnT appliance tester and that it is switched on If the device is not plugged in and the TnT appliance tester detects that no device is prese...

Page 9: ...components if fitted are checked All labels markings and warning indicators of the maximum load to be connected to the device are legible and intact The insulation is not damaged in any way i e melted...

Page 10: ...rvice Refer to the Technical Information section to change test voltage Procedure 1 Complete a Visual Inspection Only proceed if test passed 2 Plug device into appliance socket 3 Connect earth clip to...

Page 11: ...Test Ext Lead Test F3 Please Note A Visual Inspection test must be carried out before any others refer to First Test Section The Lead TEST completes the following sequence as part of its comprehensive...

Page 12: ...est to be carried out instead The TNT Series appliance testers have been designed to perform these tests The Leakage Test applies power to the Device Under Test and measures any imbalance or leakage c...

Page 13: ...ncrements The value can be changed by selecting the leakage test time in the options menu See the special functions section of the manual for more details The factory default setting is 20sec The valu...

Page 14: ...t any time The unit will power down after 20 seconds as factory default Caution This test turns the Equipment ON The power leakage test can handle up to 10 Amp Resistive Load MAX Exceeding this value...

Page 15: ...screen displays 1 option at a time You can select this option by pressing the return button To select the next item press the F2 button Pressing the F3 button escapes out of the TnT options menu Chang...

Page 16: ...Ensures appliance is plugged in and turned on Earth Bond Test 200mA test current Pass level Less than 1 0 Measurement 0 01 to 10 Insulation Test 500VDC 250VDC Pass level Greater than 1M Measurement 0...

Page 17: ...h green and device will power up Otherwise press enter to exit Warning Screen Amps Screen Watts Screen Volts Amps Screen Press the enter key to stop the power mode and return to volts Pressing F3 key...

Page 18: ...uting systems may draw from a power grid the VA is used to determine the kind of wiring and circuit breakers required to support the computing equipment in question Watts and VA Detailed Explanation T...

Page 19: ...he USB B port in the rear of the unit with USB A port on power bank using the supplied cable Press the Enter button for 2 seconds until the unit starts up To shut down the unit keep pressing the same...

Page 20: ...cations worldwide are constantly changing and that Local State and National Regulatory Authorities may also have differing or additional requirements It is strongly recommended the Purchaser check Loc...

Page 21: ...rder information TA TAGS Part no WCM TA TAG BL GN Y O BLK Colour BL Blue GN Green Y Yellow O Orange BLK Black ATT TAGS Roll of 250 These laminated generic tags come in various colours and in rolls of...

Page 22: ...th all regulations noting that extensive penalties can be imposed by the relevant authorities for any breach The IATA and other laws and regulations covering the transport of goods are very comprehens...

Page 23: ...Wavecom Instruments Portable Appliance Testers Instruction Manual 23...

Page 24: ...liance Testers Instruction Manual 24 Portable Appliance Testers TnT G4 Series www wavecom com au V010613 Note TnT Firmware TnT G4 series in general have the ability to be updated to comply with potent...