TnP Prime
User Manual
Wavecom
TnP Prime Specifications
Mains Supply Test
Checks Polarity and continuity of mains supply by LED indicators (A-N, A-E, and N-E). (Flashing red LED indicates test fail)
Class 1 Earthed Appliance
Appliance Check: Ensures appliance is plugged in and turned on.
Earth Bond Test: 200mA test current. Pass level Less than 1.0 Ω. Measurement: 0.01Ω to 10 Ω.
Insulation Test: 500VDC / 250VDC. Pass level Greater than 1M Ω. Measurement: 0.1Ω to 10MΩ. *See also Leakage Test
Class 2 Double Insulated Appliance
Appliance Check: Ensures appliance is plugged in and turned on.
Insulation Test: 500VDC / 250VDC. Pass level greater than 1MΩ. Measurement: 0.1Ω to 10MΩ. *See also Leakage Test
Extension Leads
Earth Bond Test: 200mA test current. Pass level Less than 1Ω. Measurement: 0.01Ω to 10.0Ωs
Insulation Test: 500VDC / 250VDC. Pass level Greater than 1MΩ. Measurement: 0.1Ω to 10.0MΩ.
Continuity/Polarity Test: 250VAC check continuity and polarity of leads. Displays Pass/Fail.
Leakage Test
Leakage Current: 0 to 30.0mA at 200 to 265V
Earth Leakage Test: 240VAC Mains. Pass level 1, 2.5, 5.0 mA leakage test levels with up to 10 Amp load operation (20 Amp
load for TnP Prime 20A)
Note 1: Pass level for CLASS 1 is 5 mA; pass level for CLASS 2 is 1 mA
Note 2: Leakage test may be performed if for any reason a standard CLASS 1 or CLASS 2 is not possible.
RCD Test
Trip Current: 2 to 500mA in 1mA steps. User selectable.
Trip Time: 0 to 3,000ms at .001sec resolution.
Current Ramp Trip Test: 0 to 500mA in 1mA increments.
Power Measurement
Leakage Current: 0 to 30.0mA at 200 to 265V
Load Current: 0.0 to 10Amp (20Amp for TnP Prime 20A)
Voltage: 200 to 265VAC
Power Factor: 0.00 to 1.00
Apparent Power: 0 to 2400VA
Power: 0 to 2400W
Meter Mode®
Green flashing LED denotes MM is engaged
Load Current: 0.0 to 10Amp
Voltage: 200 to 265VAC
Apparent Power: 0 to 2400VA
Power: 0 to 2400W