Installation Instructions

Please read all instructions before installing

DESCRIPTION AND OPERATION 

RH-250 Multi-way Wall Switch Convertible Occupancy Sensors are designed 

to replace standard single pole and multi-way (3-way, 4-way) switches. They 

are ideal for any room with multiple entries and any other indoor space where 

vacancy sensor-based controls with manual ON/OFF capability are desirable. 
Like standard switches, you can press the ON/OFF button to turn the light or fan 

(controlled load) ON and OFF. Unlike standard switches, the RH-250 automatically 

turns OFF the controlled load after the coverage area has been vacant for a period 

of time (Time Delay). If motion is detected within 30 seconds after it automatically 

turns OFF, the RH-250 automatically turns the load back ON.
While the sensor is factory preset as a Vacancy Sensor with manual ON operation, 

it can be adjusted to work as an occupancy sensor that turns the controlled load 

ON automatically upon detection of occupancy in the area.
The RH-250 can be wired with up to three additional RH-250s for multi-way 

Manual/Auto–ON/OFF of one or several loads (up to one load connected to each 

RH-250). It can also be wired to up to four RH-253 single pole momentary wall 

switches for multi-way Manual-ON/OFF Automatic-OFF control of one load.

Lighted Switch

To help you locate the RH-250 in a dark room, the amber LED illuminates the 

ON/OFF button while the controlled load is OFF. When the controlled load is ON, 

the LED is OFF.

Operating Modes

For multi-way operation of two or more RH-250s, we recommend that the 

Operating Mode be the same in all sensors related to the same load. This 

makes it easier to understand the multi-way control operation as well as trouble 

shooting. There are two operating modes to select from:

MODE 1

   Vacancy sensor (Manual-ON/OFF, Auto-OFF): The user must press 

the ON/OFF button to turn the load ON. The RH-250 keeps the load ON until no 

motion is detected by any of the related RH-250s for the time delay period. There 

is also a 30 second reset delay after the automatic shut-off. If motion is detected 

during this time, the sensor turns the load back ON automatically. After the 30 

second reset delay has elapsed, the ON/OFF button must be pressed to turn ON 

the load.

MODE 2

   Occupancy sensor (Auto-ON/OFF with manual control and reset to auto 

SPECIFICATIONS

Voltage   ........................................................................ 120VAC, 60Hz

Load (Multi-Way)

  Incandescent or fluorescent ......................................  0-600 Watts

  Fan motor ............................................................................ 1/6 hp

Time Delay Adjustment .................... 15 sec., 5 min., 15 min., 30 min.

Light Level Adjustment ................................................. 10 fc to 150 fc

Environment ............................................................... Indoor use only

  Operating Temperature ..........................32° to 131°F (0° to 55°C)

 Humidity ................................................ 95% RH, non-condensing

Tools Needed

  Insulated Screwdriver

  Wire Strippers

Call 800.879.8585 for Technical Support

RH-250

Multi-Way Wall Switch

Convertible

Occupancy Sensor 

Santa Clara, CA 95050

Summary of Contents for RH-250-W

Page 1: ...oad Lighted Switch To help you locate the RH 250 in a dark room the amber LED illuminates the ON OFF button while the controlled load is OFF When the controlled load is ON the LED is OFF Operating Mod...

Page 2: ...es and a coverage area of 600 square feet 56 square meters The sensor must have a clear and unobstructed view of the coverage area Objects blocking the sensor s lens may prevent detection thereby caus...

Page 3: ...m the circuit in the other wiring box to the white wire on the auxiliary RH 250 Connect the power wire from the circuit box HOT to the black wire on the auxiliary RH 250 and to the TRAVELER 1 wire Con...

Page 4: ...DOOR USE ONLY L L Red LOAD power to lamp or fan GROUND TERMINAL GROUND TERMINAL White NEUTRAL Yellow TRAVELER 2 to RH 253 TRAVELER 1 to RH 250 Black Traveler 1 power via RH 253 RH 253 HOT power from c...

Page 5: ...ing Do not overturn the Time Delay adjustment trimpot Adjusting the Light Level This feature is factory set at maximum so that even the brightest light will not prevent the sensor from turning the loa...

Page 6: ...onds to 30 minutes Check the time delay setting for each RH 250 in your multi way configuration Ensure that all RH 250s have the same time delay setting Ensure that there is no movement within the cov...

Page 7: ...gado manual o autom tico de una o varias cargas hasta una carga por cada RH 250 desde varios lugares Tambi n puede ser conectado hasta con cuatro interruptores moment neos unipolares RH 253 para el co...

Page 8: ...orea el nivel de luz natural en su rea Cualquiera de los sensores que detecte movimiento y que determine que la luz natural es insuficiente encender la carga Para ajustar el Nivel de Luz Natural por f...

Page 9: ...ac nicamente para designar el sensor que esta conectado directamente a la carga controlada Conecte el cable de LINEA o FASE del circuito al cable negro del RH 250 auxiliar y al cable VIAJERO 1 Conect...

Page 10: ...on ctelos en paralelo como se muestra ac RH 250 Rojo Tierra Amarillo Negro Blanco Carga Viajero 2 Linea Fase Neutro Viajero 1 Linea Fase TOP INDOOR USE ONLY RH 253 RH 253 Tierra Viajero 1 Viajero 1 Vi...

Page 11: ...re la perilla de ajuste del Retardo de Apagado Ajuste del Nivel de Luz Natural Esta funci n vendr configurada de f brica a su valor m ximo de tal forma que aun la luz natural m s brillante no evitar q...

Page 12: ...ardo de apagado puede ser configurado desde 15 segundos hasta 30 minutos Corrobore el valor de Retardo de Apagado en cada RH 250 Aseg rese de que todos los RH 250 tienen el mismo valor Aseg rese de qu...

Reviews: