SPECIFICATIONS
HB-480R2 Power Module
Voltages . . . . . . . . . . . . . . . . . . . . . . . . . .347/480VAC, 60Hz
Load Requirements
@ 480VAC, 60Hz . . . . . . . . . . . . . . . . . . .1200W ballast
@ 347VAC, 60Hz . . . . . . . . . . . . . . . . . . .1200W ballast
US Patents: . . . . . . . . . .4,787,722 • 4,874,962 • 5,124,566
* x indicates Control Module/Lens number. See Coverage Guide.
H B - 4 8 0 R 2 - x *
High Bay • Line Vo l tage • Pa ss i ve Infra red
O ccupancy Sensor Power Module
IMPORTANT START-UP INFORMATION
When the control module is installed and power is connected, it may take up
to a minute before the lights turn on due to a sensor warm-up period required
during initial power-up. This occurs during installation or after a power failure
of 5 minutes or more only.
If the power module is installed and powered, and no control module is in
place, the load comes on and remains on until the control module is installed.
DESCRIPTION AND OPERATION
The HB-480R2-x occupancy sensors turn lighting on and off based on
occupancy. They are designed for warehouse and high bay applications.
Careful consideration must be given to sensor placement. Avoid placing the
sensor where shelving or other obstructions may block the sensor’s line of
sight.
The HB sensors are modular and are made up of two parts, a Power Module
(HB-480R2) and a Control Module (HB-x). The HB-480R2 operates at 480VAC
or 347VAC, 60 Hz.
COVERAGE
Coverage patterns, density and range, are determined by the type of Control
Module attached to the HB-480R2.
For a complete description of each Control Module’s coverage pattern, see
the HB-x Control Module COVERAGE GUIDE.
Fig 1:
Ceiling Mount Assembly
Fig 2:
Fixture Mount Assembly
Control Module
(HB-2 shown)
HB-480R2
Power Module
Junction Box
Fixture
CP-1 J-Box
Adapter
Plate
1.
Connect the existing wires to the sensor
leads.
• Do not allow bare wire to show.
• Make sure all connections are secure.
2.
Remove the Control Module from the
HB-480R2 as shown in Fig. 7.
3a. Ceiling Mount (See Fig. 1):
• Secure the CP-1 J-Box adapter plate
to the junction box.
• Attach the sensor to the adapter plate
using four #6 x
3
/
4
” self tapping screws.
3b. Acoustic Tile or Fixture (See Fig. 2):
• Cut a hole in the mounting surface
using the “HB Cut-Out” template.
• Use four #6 x
3
/
4
” self tapping screws
to attach the sensor to the mounting
surface.
4.
Reconnect the Control Module onto the
HB-480R2 as shown in Fig. 4.
• CAREFULLY align the four connector
pins on the HB-480R2 with the
receptacles on the Control Module.
• Snap the HB-480R2 Power Module to
the Control Module using firm pressure
until they click into position at the top
and bottom.
5.
Restore power from the circuit breaker.
INSTALLATION
Fig 3:
Flying lead
c o n n e c t i o n s
Fig 4:
Connecting the
C o n t rol Module to the
H B-480R2 Power Module.
CAUTION
TURN THE POWER OFF AT THE CIRCUIT
BREAKER BEFORE INSTALLING THE SENSOR.
Fig 5: 4 8 0 VAC wiring
WIRING
Fig 6: 3 4 7 VAC wiring
MOUNTING THE SENSOR