 Wiring one CH-250 and one RH-253 single pole momentary 

 

switch for multi-way Manual-ON/OFF single load control.

IMPORTANT: The CH-250 must be installed in the 

wiring wall box that connects to the load.

•  Connect the green or non-insulated (copper) GROUND wire in each wiring box 

to the green terminal on each CH-250 and RH-253.

•  Connect the NEUTRAL wire from the circuit and from the lamp (LOAD) to the 

white wire on the CH-250.

•  Connect the power wire from the circuit box (HOT) to one terminal of the 

RH-253 single pole momentary wall switch and to the TRAVELER 1 wire.

•  Connect the TRAVELER 1 wire coming from the RH-253 wiring box to the black 

wire of the CH-250.

•  Connect the lamp power (LOAD) to the red wire on the CH-250.
•  Connect the TRAVELER 2 wire to the other side of the RH-253 single pole 

momentary wall switch and to the yellow wire of the CH-250.

CH-250

 

TOP

INDO

OR U

SE O

NLY

L

L

Red -> LOAD

(power to lamp 

or fan)

GROUND

TERMINAL

GROUND

TERMINAL

White -> 

NEUTRAL

Yellow-> TRAVELER 2 

               to RH-253

TRAVELER 1

               to CH-250

Black-> Traveler 1

      power via RH-253

RH-253

HOT (power from 

                      circuit box)

TRAVELER 2

   to CH-250

Fig. 6: Step 4b. Sensor orientation and wire connections for 3-way operation     

with an RH-253 momentary wall switch

To wire up to four RH-253 single pole momentary wall switches to one 

CH-250, wire them in parallel as shown in the following wiring diagram.

CH-250

Red

Ground

Yellow

Black

White

Load

Traveler 2

Hot

Neutral

Traveler 1 (Hot)

TOP

INDOOR USE ONLY

RH-253

Ground

RH-253

Ground

Ground

Traveler 2

Traveler 1

Traveler 2

Traveler 1

Traveler 2

Traveler 1

Fig. 7: Step 4b. Reference wiring diagram for multi-way operation with RH-253 

momentary wall switches (4 maximum)

5.   Put all the new switches into their wall boxes.

  Position the CH-250 switch(es) with the lens above the ON/OFF button (lens at 

top, ON/OFF button at bottom). Use the captive screws on the mounting strap 

to secure the switches to their wall boxes. 

6.   Restore power to the circuit.

  Turn on the breaker or replace the fuse. 

7.   Make any necessary adjustments.

  See the SENSOR ADJUSTMENT section for information. 

8. Install cover plate. 