Regulation type:
-
HYs
: regulation of hysteresis
-
bP
: regulation of proportional type
Factory setting value:
bP
Other values:
HYs
hysteresis value:
This menu is displayed only if parameter “typ” is equal to
“HYs”. Use and keys to set hysteresis value. The setting
is validated with key .
Default value:
0.3°c
Value range:
0.2°c
to
3°c
Choice of concrete type:
Two choices are possible:
-
uf1
: for thin liquid concrete < 6 cm
-
uf2
: for traditional concrete with a thickness higher than 6 cm
if parameter #26 is set to “HYs” this menu is not available.
Factory setting value:
uf1
Other values:
uf2
Choice of coating:
Two choices are possible:
-
bP1
: for tiling
-
bP2
: for wooden floors (floating or not)
if parameter #26 is set to “HYs” this menu is not available.
Factory setting value:
bP1
Other values:
bP2
Function of pilot wire:
This option is used to enable the pilot wire functionality if it’s
used on your installation.
Factory setting value:
no
Other values:
yes
Minimum value of setting range of the set point
temperature:
Factory setting value:
5.0°c
Other values:
5.0°c
to
15.0°c
Maximum value of setting range of the set point
temperature:
Factory setting value:
37.0°c
Other values:
20.0°c
to
37.0°c
humidity set point (Optional)
Factory setting value:
75 %
Other values:
0% (“no”)
to
100%