The actuator tolerates voltage fluctuation of the electrical grid up to ± 10 % of its nominal system operating voltage
2)
The actuator tolerates temporary overvoltage of the electrical grid
VTX600 VTX1000
Location
Materials
Housing: Alu EPOXY paint
Drive : Steel + Zn treatment
Shaft and screws : Stainless steel
Sealing
IP68
Extended environmental conditions
(IEC61010)
Both inside and outside (wet environments possible)
Operating temperature
-20 °C to +63 °C
Operating altitude
Up to 2000 m
Hygrometry
maximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly to 50 %
relative humidity at 40 °C
Pollution degree
Applicable POLLUTION DEGREE of the intended environment is 2
(in most cases).
Weight
25 kg
Mechanical data
Nominal torque
450 Nm
600 Nm
Maximum torque
600 Nm
1000 Nm
Operating time (90°)
42 s
65 s
Angular range
90° (180°-270° on request)
Duty cycle (
IEC60034
) 50
%
Drive ISO5211
Star 36 (depth 41 mm) • F10/F12 (depth F10 : 25 mm / F12 : 30 mm)
Manual control
Secured hand wheel without clutching system
Electrical data
Voltages
1)
230 V AC (50/60 Hz) • 3-phase 400 V (50 Hz)
Overvoltage category
2)
Power
250 W
Torque limiter
Mechanical
Number of feedback switches
2 (4 on request)
Limit switches maximum voltage
4 to 250 V AC/DC (Overvoltage category II)
Limit switches maximum current
1 mA to 5 A max
Anticondensation heaters
10 W
Rated current
400 V: 0,45 A (cos
= 0,8) • 230 V: 1,3 A (cos
= 0,8)
ATEX / IECEx
ATEX : II 2 G D Ex db IIB T5 Gb Ex tb IIIC T90°C Db LCIE 15 ATEX 3012 X
IECEx LCIE 15 0074X
Technical data