Step 7 - Wiring

Remove the wiring terminal block by pulling up from the blue sensor disk. Connect 

the 4 conductor wire to the yellow (YEL), blue (BLU), red (RED) and black (BLK) 

wiring terminations. If the installed 4 conductor cable uses a different color code, 

then make a note of the wire color versus the wiring terminal color names. Push 

the wiring terminal plug onto the pins of the blue sensor disk. At the Snow Melting 

Control location, connect the corresponding wires to the yellow, blue, red and 

black wire terminations. 

YEL

BLU

RED

BLK

Sno

w Sensor 095

Ae

rial Mounting

Designed & Assembled in Canada www

.tekmarControls.com

Step 6 - Mounting

The conduit pole can be either PVC plastic or rigid metal. The conduit pole should 

be mounted plumb using a level.
•  When using PVC plastic conduit a nominal 1/2” (16mm) PVC male terminal 

adapter with locknut is recommended.

•  When using rigid metal, a nominal 1/2” (16mm) rigid metal conduit adapter with 

set screw is recommended.

1.  Pull the 4 conductor wire through the conduit.
2. Install the sensor body with conduit adapter to the conduit. For PVC conduit 

use PVC cement adhesive.  For rigid metal conduit, tighten the set screw until 

the conduit adapter is firmly attached to the conduit.

3. Fish the 4 conductor wire though the sensor body and place on top of the 

conduit adapter. Point the sensor body towards the prevailing wind direction, if 

any. Thread the locknut onto the conduit adapter and screw until tight. 

Summary of Contents for Tekmar WiFi Snow Melting Control 670

Page 1: ...ng snow and allows a tekmar Snow Melting Control to automatically start the snow melting equipment System stop is provided by the control s timer or by manual disable The 095 mounts to a nominal 1 2 1...

Page 2: ...d contact your wholesaler or tekmar sales representative for assistance Type 095 includes One Snow Sensor 095 One Installation and Operation Manual 095_D Step 2 Choosing a Location for the Sensor The...

Page 3: ...ded cable one end of the shield wire should be connected to the Com terminal on the Snow Melting Control and the other end should remain free The shield must not be connected to earth ground 1 Remove...

Page 4: ...ntrols com Step 6 Mounting The conduit pole can be either PVC plastic or rigid metal The conduit pole should be mounted plumb using a level When using PVC plastic conduit a nominal 1 2 16mm PVC male t...

Page 5: ...300 000 Ohms 3 Measure the resistance between the red RED and black BLK wiring terminals This reading should be between 45 to 47 Ohms If resistance readings are outside of the normal operating range t...

Page 6: ...2 29 996 40 4 26 099 45 7 22 763 50 10 19 900 55 13 17 436 60 16 15 311 65 18 13 474 70 21 11 883 75 24 10 501 80 27 9 299 85 29 8 250 Temperature Resistance F C 90 32 7 334 95 35 6 532 100 38 5 828 1...

Page 7: ...0 4 lbs 180 g Dimensions 1 15 16 H x 3 5 32 O D 50 H x 80 O D mm Enclosure White PVC plastic UV stable NEMA type 1 Operating range 40 to 122 F 40 to 50 C Compatible equipment tekmar Snow Melting Contr...

Page 8: ...r labor to remove or transport the defective Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purchaser s agreement and warranty with its custom...

Reviews: