Temperature vs. Resistance Table

Temperature

Resistance

°F

°C

-50

-46

490,813

-45

-43

405,710

-40

-40

336,606

-35

-37

280,279

-30

-34

234,196

-25

-32

196,358

-20

-29

165,180

-15

-26

139,402

-10

-23

118,018

-5

-21

100,221

0

-18

85,362

5

-15

72,918

10

-12

62,465

15

-9

53,658

20

-7

46,218

25

-4

39,913

30

-1

34,558

35

2

29,996

40

4

26,099

45

7

22,763

50

10

19,900

55

13

17,436

60

16

15,311

65

18

13,474

70

21

11,883

75

24

10,501

80

27

9,299

85

29

8,250

Temperature

Resistance

°F

°C

90

32

7,334

95

35

6,532

100

38

5,828

105

41

5,210

110

43

4,665

115

46

4,184

120

49

3,760

125

52

3,383

130

54

3,050

135

57

2,754

140

60

2,490

145

63

2,255

150

66

2,045

155

68

1,857

160

71

1,689

165

74

1,538

170

77

1,403

175

79

1,281

180

82

1,172

185

85

1,073

190

88

983

195

91

903

200

93

829

205

96

763

210

99

703

215

102

648

220

104

598

225

107

553

Summary of Contents for Tekmar WiFi Snow Melting Control 670

Page 1: ...ng snow and allows a tekmar Snow Melting Control to automatically start the snow melting equipment System stop is provided by the control s timer or by manual disable The 095 mounts to a nominal 1 2 1...

Page 2: ...d contact your wholesaler or tekmar sales representative for assistance Type 095 includes One Snow Sensor 095 One Installation and Operation Manual 095_D Step 2 Choosing a Location for the Sensor The...

Page 3: ...ded cable one end of the shield wire should be connected to the Com terminal on the Snow Melting Control and the other end should remain free The shield must not be connected to earth ground 1 Remove...

Page 4: ...ntrols com Step 6 Mounting The conduit pole can be either PVC plastic or rigid metal The conduit pole should be mounted plumb using a level When using PVC plastic conduit a nominal 1 2 16mm PVC male t...

Page 5: ...300 000 Ohms 3 Measure the resistance between the red RED and black BLK wiring terminals This reading should be between 45 to 47 Ohms If resistance readings are outside of the normal operating range t...

Page 6: ...2 29 996 40 4 26 099 45 7 22 763 50 10 19 900 55 13 17 436 60 16 15 311 65 18 13 474 70 21 11 883 75 24 10 501 80 27 9 299 85 29 8 250 Temperature Resistance F C 90 32 7 334 95 35 6 532 100 38 5 828 1...

Page 7: ...0 4 lbs 180 g Dimensions 1 15 16 H x 3 5 32 O D 50 H x 80 O D mm Enclosure White PVC plastic UV stable NEMA type 1 Operating range 40 to 122 F 40 to 50 C Compatible equipment tekmar Snow Melting Contr...

Page 8: ...r labor to remove or transport the defective Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purchaser s agreement and warranty with its custom...