background image

7 of 12

User Interface - Indicator LED

Power

•  On when 115 V (ac) is applied.
•  Off when power disconnected or transformer fuse is 

blown.

Priority

•  On when zone 1 has priority over zone 2. 
•  Flashing while in priority override.

RoomResponse

TM

•  On when modulating condensing boiler is operating 

below maximum setting.

Zone 1

•  On when thermostat 1 calls for heat.

Zones 2

•  On when thermostat 2 calls for heat.
•  Off during priority operation.
•  Off when corresponding thermostat stops calling for 

heat.

Sequence of Operation

Zone Operation

When a thermostat calls for heat by closing the R and W 

terminals:
•  115 V (ac) is applied to the corresponding circulator pump.
•  The corresponding zone indicator LED is turned on.

Boiler Operation

When a thermostat calls for heat by closing the R and W 

terminals:
•  The boiler end switch XX is closed to fire the boiler. 

This requires the control DIP switch to be set to 

Master.

•  The RoomResponse

TM

 0-10 V (dc) or 4-20 mA signal is 

sent to a modulating-condensing boiler.

DHW Operation

Many modulating-condensing boilers have multiple tem-

perature call inputs. Wire the DHW end switch to input 

recommended in the boiler's manual.
When a zone 1 calls for heat by closing the R and W terminals:
•  The DHW end switch is closed to fire the boiler at the 

DHW temperature.

•  The Mod Boiler output is changed to 10 V (dc) or 20 mA.

Priority Override

•  The Priority LED light flashes when priority override is 

in effect. 

•  Priority for zone 1 is in effect for 60 minutes after 

which priority override starts by shutting off zone 1 

and resumes heating on zone 2 and expansion zones. 

•  During priority override, the mod max dial setting 

limits the RoomResponse

TM 

signal to the boiler.

Master / Member DIP Switch

•  Allows for unlimited expansion using additional 

Switching Relays and/or Zone Valve Controls.

•  The Master Switching Relay is wired and operates the 

boiler.

•  If using a single Switching Relay set to Master.
•  When using multiple Switching Relays and/or Zone 

Valve Controls, set one control to Master and set all 

other controls to Member.

•  The boiler end switch XX only closes when the DIP 

switch is set to Master and does not close when set to 

Member.

T-Stat 1 Priority DIP Switch

When T-Stat 1 is calling for heat by closing the R and W 
terminals:

•  115 V (ac) is applied to the zone 1 circulator pump.
•  Zone 1 indicator LED is turned on.
•  Priority indicator LED is turned on.
•  Zone 2 circulator pumps and LEDs are turned off.
•  Expansion Member controls shut off their zones.
•  After 60 minutes of continuous zone 1 call for DHW 

heating the control goes into priority override. This 

prevents building freeze up if the DHW tank aquastat 

fails in the closed position.

Exercising DIP Switch

•  ON: Each circulator pump is energized for 30 

seconds every 72 hours.

•  OFF: Circulator pump exercising disabled.

Post Purge DIP Switch

•  ON: After the last thermostat stops calling for heat, 

the last circulator pump remains on for 2 minutes to 

purge heat from the boiler to the zone.

•  OFF: Post purge disabled.

Mod Boiler DIP Switch

•  Select either 0-10 V (dc) or 4-20 mA signal to the 

modulating condensing boiler. Consult the boiler 

manual to determine the signal type. The DIP switch 

position does not matter if the modulating boiler 

output is not used.

Fuses

•  All fuses are T5A 250V slow blow, glass 5 x 20 mm.
•  Fuses 1 and 2 correspond to the zone 1 and 2 

circulator pump output. If a fuse is blown, first check 

that the pump is not seized and the wiring is not 

shorted. Then replace the fuse.

•  Fuse 7 and 8 correspond to the 24 V (ac) transformer 

power supply. If a fuse is blown, first check that the 

thermostat wiring is not shorted. Then replace the 

fuse.

Expansion Terminals

•  Connect the five wires of the expansion bus from the 

master to the member controls.

Terminal Description

A/tN4

Away signal connecting tekmar thermostats

B

RoomResponse

TM 

signal from member controls

C

Power common

D

Demand signal. 0 Vdc = demand. 2 Vdc = no 
demand

E

Priority signal. 0 Vdc = priority. 2 Vdc = no priority 

Summary of Contents for Switching Relay 303P Series

Page 1: ...ting to a zoned hydronic heating system RoomResponseTM signal Compatible with all low voltage thermostats Unlimited zone expansion Zone priority Priority override Pump exercising Post purge Away signal shared between tekmar thermostats Features LED for each zone priority end switch and RoomResponseTM Four ground screws Top bottom and back conduit knockouts Fuses protect transformers and pumps Two ...

Page 2: ... if not avoided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read manual and all product labels BEFORE using the equipment Do not use unless you know the safe and proper operation of this equipment Keep this manual available for easy access by all users Replacement manuals are av...

Page 3: ...screwdriver Needle nose pliers Wire stripper 18 AWG LVT solid wire low voltage connections 14 AWG solid wire line voltage connections Four 1 8 1 wood screws 1 Switching Relay 302P 2 Spare fuses located in cover Installation Manual 302P_D Keep the control dry Avoid potential leakage onto the control Maintain relative humidity less than 90 in a non condensing environment Avoid exposure to extreme te...

Page 4: ...cable Away C R Rh W R W 70 FUSE 2 FUSE 7 FUSE 8 FUSE 3 FUSE 4 FUSE 5 FUSE 6 70 80 90 60 50 100 MOD MAX MASTER MEMBER OFF OFF OFF 4 20 mA T STAT 1 PRIORITY 0N EXERCISING ON POST PURGE ON MOD BOILER 0 10V RESERVED FUSE 1 120 VAC POWER MOD X X tN4 POWER ROOM RESPONSE T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 PRIORITY PUMP 1 PUMP 2 PUMP 3 PUMP 4 PUMP 5 PUMP 6 L N L N L N L N L N ...

Page 5: ...ot required Away C R Rh W 70 FUSE 2 FUSE 7 FUSE 8 FUSE 3 FUSE 4 FUSE 5 FUSE 6 70 80 90 60 50 100 MOD MAX MASTER MEMBER OFF OFF OFF 4 20 mA T STAT 1 PRIORITY 0N EXERCISING ON POST PURGE ON MOD BOILER 0 10V RESERVED FUSE 1 120 VAC POWER MOD X X tN4 POWER ROOM RESPONSE T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 PRIORITY PUMP 1 PUMP 2 PUMP 3 PUMP 4 PUMP 5 PUMP 6 L N L N L N L N L ...

Page 6: ...10V RESERVED FUSE 1 120 VAC POWER MOD X X tN4 POWER ROOM RESPONSE T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 PRIORITY PUMP 1 PUMP 2 PUMP 3 PUMP 4 PUMP 5 PUMP 6 L N L N L N L N L N L N L N tN4 A C R W tN4 A C R W T STAT 4 tN4 A C R W T STAT 5 tN4 A C R W T STAT 6 EXPANSION tN4 A C R W tN4 A B C D E FUSE 2 FUSE 7 FUSE 8 FUSE 3 FUSE 4 FUSE 5 FUSE 6 70 80 90 60 50 100 MOD MAX MAST...

Page 7: ... Switching Relay set to Master When using multiple Switching Relays and or Zone Valve Controls set one control to Master and set all other controls to Member The boiler end switch XX only closes when the DIP switch is set to Master and does not close when set to Member T Stat 1 Priority DIP Switch When T Stat 1 is calling for heat by closing the R and W terminals 115 V ac is applied to the zone 1 ...

Page 8: ...e Master Mod Max Max Voltage Max mA 50 5 12 60 6 13 6 70 7 15 2 80 8 16 8 90 9 18 4 100 10 20 FUSE 6 70 80 90 60 50 100 MOD MAX Mod Max dial set to 100 in the illustration Boiler Make Model Required Adapter Supplied by boiler manufacturer 0 10 V dc 4 20 mA DIP Switch Mod Max Dial for Boiler Design Temperature 120 F 140 F 160 F 180 F Aerco AM series Not required 0 10 V 50 65 80 100 Bosch Greenstar ...

Page 9: ... Change Energy Management setting Central Heat Modulation Source to 4 20 mA Change Energy Management setting Central Heat 4 20 mA Setup 4 mA Water Temperature to 80 F 26 5 C 9 10 22 23 5 6 16 17 2 U 1 X X T T 1 2 9 10 No changes to the boiler are required On the V10 controller Set Load 1 to External Control Change Max Control 9 5 Vdc to 190 F 88 C Change Min Control 2 1 Vdc to 32 F 0 C IBC V10 Con...

Page 10: ...etpoint source to 4 20mA Enter boiler password Set Parameter Setpoint source to 4 20mA Lochinvar Knight Lochinvar FTXL NTI Trinity LX Riverside HeatStation NTI Trinity Fire Tube 302P 302P 302P 302P 302P Sensor I O 24Vac I O X X W R 1 2 37 38 X X W R 21 22 35 36 X X CH1 R 3 5 11 12 X X CH1 R 3 5 4 5 8 EMS 9 Laars Mascot FT Peerless Pinnacle Terminal Strip Peerless Pinnacle Control Board Peerless PF...

Page 11: ...P 302P 302P 1 4 1 2 5 6 Connect to the Viessmann Extension Module EA1 Plug 0 10V Switching Relay 302P Two Zones with Priority Literature Submittal 302P_C Installation Manual 302P_D Job Record 302P_J Packaged weight 5 0 lb 2250 g Dimensions 8 3 16 H x 10 11 16 W x 2 3 8 D 208 x 271 x 60 mm Enclosure Cover ABS plastic Base galvanized steel NEMA type 1 Approvals CSA C US RoHS Ambient conditions Indoo...

Page 12: ... made by Pur chaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser s sole responsibility and obligation Purchaser shall indemnify and hold tekmar harmless from and against any and all claims liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers ...

Reviews: