2

Watts Series 709 Double Check Valve 
may be installed in either a vertical or hori-
zontal position.
Install valve in the line with arrow on valve 
body pointing in the direction of fl ow.
They should always be installed in an 
accessible location to facilitate testing 
and servicing.
Pipe lines should be thoroughly fl ushed to 
remove foreign material before installing 
the unit. A strainer should be installed as 
shown, ahead of backfl ow preventers to 
prevent discs from unnecessary fouling.

CAUTION:

 Do not install with strainer 

when backfl ow preventer is used on sel-
dom-used water lines which are called 
upon during emergencies, such as fi re 
sprinkler lines, etc.
It is important that Series 709 be tested 
periodically in compliance with local 
codes, but at least once a year or more 
often, depending upon system conditions. 
(Send for IS-TK-7).

Indoor Installations

For indoor installations, it is important that 
the valve be easily accessible to facilitate 
testing and servicing.

Outdoor Installations

In area where freezing conditions do not 
occur, Series 709 can be installed outside of 
a building. The most satisfactory installation 
is above ground and should be installed in 
this manner whenever possible.
It is generally recommended that backfl ow 
preventers never be placed in pits unless 
absolutely necessary and then only when 
approved by local codes. In such cases, 
a modifi ed pit installation is preferred 
or an insulated above ground insulated 
enclosure.

Vertical

Horizontal

Watts 709S
2

1

2

" – 10"

Strainer

Indoor Installations

  

  mm A  

mm

 2

1

2

" – 3"  65-80 

10" 

300

 4 

 

100 15"  450

 6 

 

150 15"  450

 8 

 

200 23"  680

 10 

250  25"  750

Clearance Required 

for Servicing

A

Now Available, 

WattsBox Insulated 

Enclosures.

 

For more information, send for ES-WB 

or ES-WB-T.

Above Ground in Insulated Enclosure

For indoor installations, it is important that the valve be 
easily accessible to facilitate testing and servicing.

Outdoor Installations

Meter

Strainer

Watts 709S

2

1

2

" – 10" (65-250mm)

Basic Installation Instructions

RP-IS-709_709DCDA.indd   2

9/26/08   2:28:14 PM

Summary of Contents for Series 709

Page 1: ... sentative on back page IMPORTANT Inquire with governing authorities for local installation requirements NOTE For Australia and New Zealand line strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer Its important that this device be tested periodically in compliance with local codes but at least once per year or more as service conditions warrant ...

Page 2: ... it is important that the valve be easily accessible to facilitate testing and servicing Outdoor Installations In area where freezing conditions do not occur Series709canbeinstalledoutsideof abuilding Themostsatisfactoryinstallation is above ground and should be installed in this manner whenever possible Itisgenerallyrecommendedthatbackflow preventers never be placed in pits unless absolutely nece...

Page 3: ... Test 6 Close shutoff valve No 2 then No 1 7 Slowly open VA and lower high side pressure about 2 psid below the low side pressure differential read ing about 2 0 psid Close VA If reading is maintained record as tight If reading returns to 0 and the pressure A increases to pressure B the check is recorded as leaking If the reading returns to psid No 2 shutoff valve is leaking excessively and must b...

Page 4: ... RK 709 C2 11 2 2 32 50 Kit includes Cover and Cover o ring Stainless Steel 1 After removing the cover screw the check comes out with the cover 2 Holding the check Valve module in both hands rotate the assembly 1 4 turn This will disengage the disc and spring assembly into individual components The disc assembly may be cleaned or replaced O rings should becleanedorreplacedasnecessaryandlightlygrea...

Page 5: ...er O ring Complete Rubber Parts 0887915 RK 709 RT 21 2 3 65 80 0887916 RK 709 RT 4 100 0887917 RK 709 RT 6 150 0887918 RK 709 RT 8 200 0887919 RK 709 RT 10 250 Kit includes Two discs and Two Cover O rings Seat Kits 0887910 RK 709S 21 2 3 65 80 0887911 RK 709S 4 100 0887912 RK 709S 6 150 0887913 RK 709S 8 200 0887914 RK 709S 10 250 Kit includes Seat Seat o ring Retainer Wire and Cover O ring Cover ...

Page 6: ...s vent Installed At All cross connections subject to backpressure or back siphonage where there is a high potential health contamination Continuous pressure Fire protection system supply main Detects leaks and unauthorized use of water All cross connections subject to backpressure or back siphonage where there is a low potential health contamination Continuous pressure Fire protection system suppl...

Page 7: ...emble clean or replace check open e Weak or broken spring Disassemble and replace spring 2 Chatter during flow a Worn damaged or Disassemble and repair or conditions defective guide replace guide 3 Low flows passing a Mainline check fouled Disassemble and clean through mainline valve 709DCDA only b Meter strainer plugged Disassemble and clean c Damaged mainline seat Disassemble and replace disc or s...

Page 8: ...r breach of warranty and the Company shall not be responsible for any incidental special or consequential damages including without limitation lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water condi...