Operation & Maintenance Manual 

AquaSolve

®

IOM-M8408_M8410-COM_EN

Page 7 of 8

Technical Support

  •  (800) 433-5654  •  Mon-Fri, 8 am - 5 pm EST

Replacing the Media

1.  Shut off the primary feed supply going to the 

AquaSolve tank.

2.  Open up a downstream spigot or faucet to release 

pressure in the tank and in the distribution lines 
before and after the system.

3.  Shut the isolation valves immediately before and 

after the tank.

4.  Place into By-Pass position.
5.  Using a step ladder and strap wrench, remove 

the threaded head assembly connection (turning 
counter-clockwise) and remove the complete upper 
assembly including PVC upper basket. Rinse these 
parts in a nearby sink or bucket of water. Do not 
drain the tank.

6.  Remove the distributor tube with the bottom strain-

er. Rinse these parts in a nearby sink or bucket of 
water.

7.  Get a 6ft length of 3/4” sch. 40 PCV and a length 

of 1” polyvinyl hose. The length of hose depends 
on the distance to the nearest floor drain. (Both of 
these can be acquired at Home Depot or Lowes.)

8.  Insert one end of the pipe inside the hose and put 

the other end of the pipe into the top of the tank 
and down into the media. Put the other end of the 
hose inside a rice bag and put the rice bag on the 
floor drain.

9.  Get a garden hose and put it on the open end of 

the poly hose to fill the hose and pipe with water. 
Air will bubble out of the tank. Once all the air is 
out of the hose and pipe, you can start a siphon to 
remove the media. Put the garden hose in the top 
of the tank and turn it on to keep the tank full of 
water. Push the pipe up and down in the media to 
get it all out. The rice bag will catch the media and 
allow the water to go down the drain.

10.  Try not to be too aggressive when extracting the 

media. You need to take it out in small bites. If you 
let the whole pipe/ hose fill with media it will plug 
up. You need to let slugs of water flush out the pipe 
as you go.

11.  When all the old media is removed turn off the gar-

den hose and continue to siphon until the tank is 
about half full with water.

Your AquaSolve media should be replaced every 3 years.

NOTICE

12.  Reinstall the distributer tube with bottom strainer 

that was removed in step 6. Center the distributor 
tube in the bottom of the tank. Keeping any and 
all media from entering the distributor tube, cap 
the top open end of the distributor tube with plas-
tic sheeting and tape. Test it to make sure it will 
not come off during the media loading process. 
Carefully pour-in a new bag of media that specif-
ically meets the replacement requirement of the 
tank. For example, an M8408-COM system requires 
(x1) M8408-COM-RM Replacement Media.

13.  Inspect the threaded connection on the top of the 

tank to ensure no loose beads of media are stuck 
to the internal threads. If visible, wipe away the 
beads with a damp cloth.

14.  Re-attach the head assembly onto the distributor 

tube and thread the head assembly back onto the 
tank. Hand-tighten until the final turn when a strap 
wrench can help tighten the connection.

15.  Slowly place AquaSolve By-Pass Valve into Service 

position (see image on page 6 for reference).

16.  Purge the air at a downstream faucet close to the 

system.

17.  Once the tank is full, wait 4 hours for media to 

“hydrate”.

18.  Put the tank in service.

Alternative Method for Replacing Media

Follow steps 1 – 5 then,

•  Remove center distributor tube and lower basket 

and siphon all water from tank

•  Lay tank down on its side  

and tip upside down while  
using hose to flush  
media out

•  When all the old media is  

removed, stand tank back  
up and install in original  
position. Fill the tank so  
that it is about half full  
with water.

Then continue with  
steps 11 – 17.

Summary of Contents for PVI AquaSolve M8408-COM

Page 1: ...5 9531 Toll Free 800 784 8326 PVI com Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST Manufacturing ASME Commercial Water Heaters Since 1961 IOM M8408_M8410 COM_EN Important Read this Manual BEFO...

Page 2: ...e require adjustments AquaSolve Benefits Chemical free scale prevention and protection converts hardness minerals to harmless inactive microscopic crystals making AquaSolve an effec tive alternative t...

Page 3: ...uaSolve there are some unique requirements for using AquaSolve in conjunction with other forms of water treatment 1 AquaSolve must be the last stage in the treatment chain Do not install any filters a...

Page 4: ...scaling While silica tends to have a less significant effect on scale formation than other miner als it can act as a binder that makes water spots and scale residue outside the plumbing system difficu...

Page 5: ...o isolate the tank for servicing A full bypass should be installed so that the full service flow can be routed around the system as needed for servicing NOTICE Install Piping Connect the inlet and out...

Page 6: ...f these objects protect remove them or use the outlet hose to drain option 6 Connect the outlet of the AquaSolve system to the cold water supply to the building 7 Open the supply valve to the AquaSolv...

Page 7: ...ng the media You need to take it out in small bites If you let the whole pipe hose fill with media it will plug up You need to let slugs of water flush out the pipe as you go 11 When all the old media...

Page 8: ...ring any part or parts to our satisfaction that prove defective within the warranty period stated above Such replacement parts will be delivered to the owner F O B nearest factory at no cost excluding...

Reviews: