Operation & Maintenance Manual 

AquaSolve

®

IOM-M8408_M8410-COM_EN

Page 4 of 8

Technical Support

  •  (800) 433-5654  •  Mon-Fri, 8 am - 5 pm EST

Equipment Specifications

AquaSolve systems are complete, selfcontained, 
loaded with media, and ready to use. A simple 
inlet and outlet connection is all that is required for 
installation. Please review operating pressures, tem-
peratures and water chemistry limitations to ensure 
compatibility.

Feed Water Chemistry Requirements

pH

6.5 to 8.5

Hardness (max.)

30 grains

Water Pressure

15 psi to 150 psi

Temperature

40ºF to 100ºF (5ºC to 38ºC)

Chlorine

<2 ppm

Iron (max.)

0.3 mg/l*

Manganese (max.)

0.05 mg/l**

Copper (max.)

1.3 ppm**

Oil & H2S

Remove prior to AquaSolve

Silica (max.)

20 ppm***

TDS

500 mg/l****

*Iron and Manganese

Just as with conventional water softening media, AquaSolve needs 
to be protected from excess levels of certain metals that can easily 
coat the active surface, reducing its effectiveness over time. Public 
water supplies rarely, if ever, present a problem, but if the water 
supply is from a private well, confirm that the levels of iron (Fe) and 
manganese (Mn) are less than 0.3 mg/L and 0.05 mg/L respectively.

**Copper

Pursuant to the EPA drinking water standards, the copper concen-
tration permitted is up to 1.3 ppm. Typically originating from new 
copper plumbing, high levels of copper can foul AquaSolve media. 
For applications with copper concentration greater than 1.3 ppm, 
please contact PVI Technical Support at 1-800-433-5654. To further 
minimize any problem with excess copper, avoid applying exces-
sive flux on the inner surfaces of the pipe and use a low-corrosivity 
water soluble flux listed under the ASTM B813 standard.

***Silica

AquaSolve media does not reduce silica scaling. While silica tends 
to have a less significant effect on scale formation than other miner-
als, it can act as a binder that makes water spots and scale residue 
outside the plumbing system difficult to remove. This 20 ppm limita-
tion is for aesthetic purposes.

****Hardness Maximum for AquaSolve scale prevention operation 
is 514 mg/l as Calcium Carbonate. All other minerals and metals 
that contribute to TDS, when combined, must not exceed the 500 
mg/l Maximum Contaminant Level (MCL) for Total Dissolved Solids 
as set by the USEPA Safe Drinking Water Act (SDWA). Minerals 
and Metals must not exceed their individual MCLs established by 
the USEPA SDWA. Specific Mineral and Metal MCLs, identified in 
Watts’ published Feed Water Chemistry Requirements, supersede 
the USEPA SDWA.

NOTICE

Water known to have heavy loads of dirt and debris may require 
prefiltration prior to AquaSolve.
*See note about iron, manganese and copper (bottom left). 
Systems using AquaSolve technology prevent hard water scale 
formation inside the plumbing system at influent hardness levels 
of 30 grains per gallon of calcium carbonate and less. Due to vari-
ances in water chemistry, certain aesthetic conditions external of 
the plumbing system may not be attained. AquaSolve is designed 
for the treatment of potable water that meets the requirements of 
the current USEPA Safe Drinking Water Act.

NOTICE

Mechanical Specifications

M8408-COM

M8410-COM

Dry Weight

36 lbs / 16 kgs

49 lbs / 22 kgs

Service Weight

108 lbs / 49 kgs

182 lbs / 83 kgs

Inlet/Outlet
Connection

1” FNPT

1” FNPT

Max Service 
Flow gpm

12

20

Dimensions 

(inches)

M8408-COM M8410-COM

A

47.5

58.0

B

46.0

56.5

C

11.1

12.0

D

1.5

1.5

E

2.0

2.0

Exceeding maximum flow can reduce effectiveness and void  
warranty. Pressure drop at peak flow rate is less than 14 psi.
Pressure drop reading taken with inlet and outlet gauges installed 
at a common elevation and 80 degree feed water.

Summary of Contents for PVI AquaSolve M8408-COM

Page 1: ...5 9531 Toll Free 800 784 8326 PVI com Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST Manufacturing ASME Commercial Water Heaters Since 1961 IOM M8408_M8410 COM_EN Important Read this Manual BEFO...

Page 2: ...e require adjustments AquaSolve Benefits Chemical free scale prevention and protection converts hardness minerals to harmless inactive microscopic crystals making AquaSolve an effec tive alternative t...

Page 3: ...uaSolve there are some unique requirements for using AquaSolve in conjunction with other forms of water treatment 1 AquaSolve must be the last stage in the treatment chain Do not install any filters a...

Page 4: ...scaling While silica tends to have a less significant effect on scale formation than other miner als it can act as a binder that makes water spots and scale residue outside the plumbing system difficu...

Page 5: ...o isolate the tank for servicing A full bypass should be installed so that the full service flow can be routed around the system as needed for servicing NOTICE Install Piping Connect the inlet and out...

Page 6: ...f these objects protect remove them or use the outlet hose to drain option 6 Connect the outlet of the AquaSolve system to the cold water supply to the building 7 Open the supply valve to the AquaSolv...

Page 7: ...ng the media You need to take it out in small bites If you let the whole pipe hose fill with media it will plug up You need to let slugs of water flush out the pipe as you go 11 When all the old media...

Page 8: ...ring any part or parts to our satisfaction that prove defective within the warranty period stated above Such replacement parts will be delivered to the owner F O B nearest factory at no cost excluding...

Reviews: