Operation & Maintenance Manual
AquaSolve
®
IOM-M8408_M8410-COM_EN
Page 5 of 8
Technical Support
• (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
Installation
Tighten the tank head.
Anytime AquaSolve systems are installed above the ground floor
of a building it is recommended that a vacuum relief valve also be
installed to protect against tank collapse in the event the plumb-
ing system is drained. If a vacuum relief valve is not used then the
system should be placed in bypass anytime the plumbing system
is drained. The EDP code for the suggested vacuum relief valve is
0556031 (not included). The vacuum relief valve should be
installed on the outlet of the system.
NOTICE
• We recommend the installation of a dual-union ball-valve on
the inlet and outlet to isolate the tank for servicing.
• A full bypass should be installed so that the full service flow
can be routed around the system as needed for servicing.
NOTICE
Install Piping
Connect the inlet and outlet plumbing according to
your preferences and any applicable local codes.
Include sample/drain ports with hose-bibb connec-
tions on the inlet and outlet piping to facilitate startup
and service.
Check the head on top of the tank. It’s common for it to loosen
during shipment. Tighten the head with a strap wrench as needed.
NOTICE
Replacement Media
M8408-COM-RM Replace media every 3 years
M8410-COM-RM Replace media every 3 years
System Overview
Stainless Steel Head and By-Pass Assembly
Parts List
Item
Quantity Part #
Description
1
1
TBD
S.S. Inlet/Outlet Head
2
2
TBD
By-Pass Clips (x2) required
3
2
TBD
1” Coupling & O-Ring (x2)
required
4
1
TBD
S. S. By-Pass Assembly
5
1
TBD
8” x 44” Tank 2.5” Top
(not shown)
6
1
TBD
10” x 54” Tank 2.5” Top
(not shown)