background image

 

12 of 20

All ProMelt systems will have fluid exposed to tempera-

tures below freezing and will use propylene glycol to 

prevent the system fluid from freezing. The level of freeze 

protection will depend on the glycol concentration used.

If the system is to be filled and commissioned during 

freezing conditions, it is strongly recommended that a fill 

cart be used to fill the system with pre-mixed anti-freeze 

solution. Pre-mixing glycol with distilled water in the 

proper ratio is always the preferred method of filling the 

system. Be certain to follow the glycol manufacturer’s 

instructions for mixing, testing and maintaining the an-

ti-freeze solution.

Annual Glycol Maintenance

 

 A glycol system should be checked for two things: 

system pH and freeze  protection. The quickest way to 

check a glycol system’s pH is with litmus paper. If the 

pH drops below 7, then more buffers must be added to 

a system or the system needs to be flushed and refilled. 

There are only a limited number of times buffers can 

be added to a system before it must  be flushed and 

replaced. Check with the glycol manufacturer for further 

details. Some glycol manufacturers will require a higher 

minimum pH to be maintained. 

 

 The second item that must be checked in a glycol 

system is the actual 

level of freeze protection 

provided. Watts recom-

mends a 30-50% glycol 

solution. However, a 

50% anti-freeze solution 

and 50% water does not 

always equate to a 50% 

solution. Different glycol 

providers supply different 

concentrations of glycol 

and/or may mix a certain 

amount of  distilled water 

with the inhibitors.

The only way to accurately measure the percentage of 

glycol in a system is to  use a refractometer. A refractom-

eter determines the freeze point of a liquid by measur-

ing the angle through which light is bent (the angle of 

refraction) as it  passes through the liquid. This angle 

is a direct correlation to its freeze point, and should 

be checked before and after the glycol is added to the 

system. Check a sample mixture of one cup glycol and 

one cup water. Test this solution  with the refractome-

ter to see what the system freeze protection will be. Do 

this each time the system is re-filled with new glycol. 

Also, check the freeze protection when the system pH is 

checked just to make sure the system is operating within 

the desired parameters.

10

0

-10

-20

-30

-40

Refractometer

System Commissioning and Maintenance

When using the ProMelt 399 panel, typically only the 

snow melt side of the heat exchanger (connected to the 

snow melt manifold) is filled with anti-freeze solution.

NOTICE

Glycol Basics

Glycol is naturally corrosive. Buffers and inhibitors are 

added to offset this corrosive effect. In addition, glycol 

acts like an “oxygen grabber”, absorbing any free 

oxygen molecules in the system. The more oxygen the 

glycol “grabs”, the more acidic it will become.

Systems should not be 

operated at levels below 

30% glycol. Glycol 

levels below 25% do 

not  contain enough 

corrosion inhibitors and 

may cause the glycol 

to act as food, allowing 

microbes to grow. These 

microbes feed, grow and 

die, creating a black sludge material in the  system. 

Propylene glycol concentrations above 25% prevent 

microbial growth. It is recommended to not use a 

concentration greater than 70% as the fluid may become 

too viscous (thick) for the circulators.

As glycol in the system ages, the inhibitors and buffers 

contained in the system begin to break down. This 

process slowly returns the system to the natural pH level 

of the glycol. If not properly maintained, glycol will cause 

corrosion. Check a glycol system at least once a year to 

ensure the glycol is still within its operating parameters.

Summary of Contents for ProMelt 150

Page 1: ...Installation Operation and Maintenance Manual ProMelt Hydronic Panels Pre Configured Snow Melt Solutions ...

Page 2: ...s and other accessories are also available from www watts com radiant Replacement manuals for the snow melting controls and sensors are available from tekmarControls com This pictorial alerts you to electricity electrocution and shock hazards This symbol identifies hazards which if not avoided could result in minor or moderate injury This symbol identifies hazards which if not avoided could result...

Page 3: ...nd in the corresponding tekmar control manual WARNING CAUTION NOTICE N OT FOR P O TA B L E U S E lb WARNING CAUTION NOTICE N OT FOR P O TA B L E U S E lb WARNING CAUTION NOTICE N OT FOR P O TA B L E U S E lb N OT FOR P O TA B L E U S E WARNING CAUTION NOTICE N OT FOR P O TA B L E U S E lb Care should be taken when lifting a ProMelt panel Each panel can weigh in excess of 100 pounds and can be unev...

Page 4: ...s been discolored If the indicator has turned red the ProMelt panel has experienced excessive shock and should be reported to the freight carrier Any type of damage can result in improper opera tion both mechanically and electrically Do not attempt to fix damaged areas without obtaining written instructions from Watts Radiant on how the corrections are to be performed Receiving Product Description...

Page 5: ...iler From Boiler To Zone From Zone A C D D B E G F To Boiler From Boiler To Zone From Zone A A J C C B B D E F F H G I I ProMelt Panels Load MBH Pipe Size Max GPM Circulator Type Ph Volt Amps HP 150 1 9 0013 1 120 2 1 6 250 1 1 4 15 Panel Model Snow Melt Area Max BTUs ft2 Pipe Size Total Length 150 700 ft2 150 1 50ft 250 1200 ft2 150 1 1 4 50ft 399 2000 ft2 150 1 1 2 50ft 399 MBH ProMelt Panels A ...

Page 6: ... Cleat Brackets Circulators Each Cleat is designed to be used with a single ProMelt panel system and provides an anchor point to at least two studs three studs for HX panels Check packaging for Cleat when removing panel from packing material When selecting a ProMelt panel make sure the included circulator is capable of handling the system flow and head pressure requirements ...

Page 7: ...fted and secured in place 1 Locate where the top of the panel needs to be This will correspond to the top of the Cleat Bracket 2 Mount the Cleat Bracket using two 1 2 x 3 1 2 min long lag bolts with the smaller 150 and 250 MBH Pro Melt panels and four with the larger 399 MBH panels Ensure the bracket is level on the wall and crosses at least two studs three for HX Pre drill each bolt location with...

Page 8: ...ront of the ProMelt panel With assistance lift the ProMelt panel so the top edge sits on the Cleat Bracket Make sure the mounting holes on the brackets align with the holes on the ProMelt panel Secure the back panel to the cleat with the use of a 1 2 bolt and washer 5 Confirm the panel is level and fully engaged NOTICE P O TA B L E U S E lb ...

Page 9: ... will be necessary to install in sections The panel system will come fully assembled in the shipping crate Expansion tanks will be shipped loose in the crate First disconnect the heat exchanger before attempting to lift the assembly Failure to do so may cause the pan els to warp deforming the connecting copper Lift and mount the primary side followed by the second ary Center both panels on the Cle...

Page 10: ...rs and socket please refer to installation manuals included with the sensor packaging NOTICE ALL CONDUIT AND RELATED ACCESSORIES MUST BE INSTALLED PRIOR TO SENSOR INSTALL Use five conductor 18 AWG LVT cable for the 090 or 095 sensor and two conductor 18 AWG LVT cable for the 070 air sensor Either cable can be run up to 500 feet without impacting performance Contact the factory if a longer distance...

Page 11: ...month before the winter season This process will help ensure circulators and other components continue to function as intended This section covers general commissioning steps and procedures Refer to the specific tekmar control manual included with the ProMelt panel for complete details on system set up and operation parameters Follow all boiler manufacturer recommendations for set up wiring and op...

Page 12: ...int of a liquid by measur ing the angle through which light is bent the angle of refraction as it passes through the liquid This angle is a direct correlation to its freeze point and should be checked before and after the glycol is added to the system Check a sample mixture of one cup glycol and one cup water Test this solution with the refractome ter to see what the system freeze protection will ...

Page 13: ...V3 V1 A1 V2 V4 D1 D2 V3 All configurations must include manifold vent purge assemblies Failure to do so may result in complications purging NOTICE 10 Slowly open purge valve at manifold until water air begin flowing Remain at this position until flow is water only 11 Close manifold purge valve and D2 and replace cap s Air remains in return line from manifold 12 Open V4 13 Close D2 and disconnect f...

Page 14: ...lect Hand Duration Enter the desired run time 1 Home Screen Select Settings 2 Select Override 3 Select Manual Override 4 Select Hand type and then Back 5 Select System Pump 6 Select On then Back 7 Arrow down to Select Hand Duration to modify run times 16 Allow pumps to run until air has been vented 17 Turn off pumps and fill system to 15 psi This may need to be done several times as air will vent ...

Page 15: ... vented Do not turn off water supply 9 Turn off pumps and fill system to 15 psi System Commissioning and Maintenance Fill Secondary zone Side 1 Open valves V1 V2 V3 V4 2 Set mix valve actuator M1 to MANUAL and slowly turn to position 5 3 Open black cap on top of air vent A1 two full turns 4 Attach fill hose to D1 and begin filling Water will push air slugs into main air vent A1 through return line...

Page 16: ...n air vent A2 b Fill until air stops venting from A2 and pressurize to 15 psi Adjusting System Pressure Snow melting systems are typically subjected to temperatures well below freezing As the anti freeze solution decreases in temperature its volume will also decrease This will result in lower system pressure during the winter months when the system is not operating The minimum required operating p...

Page 17: ... c Check system pressure is at least 12psi d Check the snow melt sensor connection at the relay box verifying all operational functions are set properly see manufacturer s instructions e Verify there is flow Is the system air locked Is the circulator running Is 120V power present at circulator s tekmar control is not operating correctly a Verify circuit breaker is not tripped and 120VAC power is p...

Page 18: ...20 19 WiFi Snow Melting Control 670 Boiler Mixing Electric Date Code H2055A 1 kΩ max 1 kΩ max Opn 3 Var 2 Mix V mA 1 Pwr 4 Mix Cls 5 Blu 8 Yel 9 Brn 10 Slab Man 11 Melt C 12 Blk 7 Com Red 6 Boiler 1 ModBoiler 21 Stage 1 Boiler 1 Stage 2 Heat Relay System Pump 22 23 24 25 Do Not Apply Power Mix 15 Sup Com 16 Boil 17 Out 18 Com 14 tN4 13 28 27 26 Power 29 L 30 N Snow Sensor 095 Field Wired Appendix ...

Page 19: ... Ice Sensor 2 Do Not Apply Power 41 42 43 Pwr Floating Action Mixing Cls Opn Boiler 39 40 Pump Pump 29 30 Pump Primary System 31 32 44 45 Power In N L BACnet MSTP Modbus MSTP 16 17 18 Gnd B A RS 485 20V 3 dc 5V dc Out 0 10V 4 20mA In Out Flow Sensor Pressure Sensor In Vdc 6 Gnd 7 mA 4 5 Com 8 Boil Sup Out 9 Boil Ret 10 Com Com 11 Sys Sup 12 Sys Ret 13 14 15 1 Analog Mixing 2 Temperature Sensors Di...

Page 20: ...LITY AND FITNESS FOR A PARTICULAR PURPOSE 8 The remedy described above in this warranty shall constitute the sole and exclusive remedy for breach of warranty and apart from that remedy Watts shall not be responsible under any legal theory for any incidental special or consequential damages including without limitation lost profits or the cost of repairing or replacing other property which is damag...

Reviews: