Technical Support

  •  (800) 433-5654  •  Mon-Fri, 8 am - 5 pm EST

Installation

Tighten the tank head

*It is very important to use flexible connections on the inlet and
outlet plumbing in the horizontal orientation as shown in the imag-
es on this page. The tanks expand and contract with water pres-
sure fluctuations. Flexible connectors will prevent plumbing and 
tank leaks. The part number for the suggested Lync 2” Flexible 
Connectors is 144065 (two are included and required for installa-
tion).

Anytime 

AquaSolve

 systems are installed above the ground floor 

of a building it is recommended that a vacuum relief valve also be 
installed to protect against tank collapse in the event the plumb-
ing system is drained. If a vacuum relief valve is not used then the 
system should be placed in bypass anytime the plumbing system 
is drained. The part number for suggested vacuum relief valve is 
123318 (not included). The vacuum relief valve should be installed 
on the outlet of the system.

NOTICE

•  We recommend the installation of a dual-union ball-valve on 

the inlet and outlet to isolate the tank for servicing.

•  A full bypass should be installed so that the full service flow 

can be routed around the system as needed for servicing.

NOTICE

Install Piping

Connect the inlet and outlet plumbing according to 
your preferences and any applicable local codes. 
Include sample/drain ports with hose-bibb connec-
tions on the inlet and outlet piping to facilitate startup 
and service.

Support the Piping

2 inch Flex Connectors must be installed horizontally not vertically 
in the water pipe line. The full weight of the piping and valves must 
be supported by uni-strut, pipe hangers or other means. The tank 
connections cannot support the weight of the piping. The image 
below for a multi-tank system installation shows properly support-
ed piping.

WARNING

Start-Up

Connect a hose to the hose bibb on the outlet of 
the tank. Run the hose to a drain and open the hose 
bibb.

Slowly/partially open the supply water ball valve. 
Allow the tank to slowly fill with water. When a 

Fill in install date and rebed due date on product label located
on front of each tank as reminder to replace 

AquaSolve

 media 

every 3 years. The system is now ready for operation.

NOTICE

Typical Installation for Single and  
Multi-Bank Systems

steady stream of water appears at the drain, close 
the supply valve and hose bibb. Once the tank is full, 
wait 4 hours for media to “hydrate”.

Slowly open the inlet and outlet valves on the sys-
tem. Transfer the bypass valve from Bypass to the 
Service position. Open a nearby faucet downstream 
from the AquaSolve system to relieve any air.

Check for leaks. Repair as needed.

Check the head on top of the tank. It’s common for it to loosen 
during shipment. Tighten the head with a strap wrench as needed.

NOTICE

Operation & Maintenance Manual

Lync AquaSolve

L-OMM-010_A

Summary of Contents for Lync AquaSolve LM8414TM-COM

Page 1: ...00 Fort Worth TX 76134 817 335 9531 Technical Support 800 433 5654 ext 3 Mon Fri 8 am 5 pm CST Engineered Solutions L OMM 010_A Important Read this Manual BEFORE using this equipment Failure to read and follow all safety and use information can result in death serious personal injury property damage or damage to the equipment Keep this Manual for future reference 2021 Lync ...

Page 2: ...rystals making AquaSolve an effec tive alternative technology to a water softener for the prevention of scale due to water hardness Virtually maintenance free no control valve Uses environmentally friendly technology by using no salt or other chemicals to constantly add no electricity and no wastewater Improves efficiency of all water using appliances both hot and cold Simple sizing and installati...

Page 3: ...olve in conjunction with other forms of water treatment 1 AquaSolve must be the last stage in the treatment chain Do not install any filters after Lync AquaSolve or before any devic es for which scale prevention is required POU filters e g car bon RO or Ultraviolet UV are exempt from this requirement 2 Do not apply any other antiscalants before or after AquaSolve 3 The addition of soaps chemicals ...

Page 4: ...g AquaSolve technology prevent hard water scale formation inside the plumbing system at influent hardness levels of 30 grains per gallon of calcium carbonate and less Due to vari ances in water chemistry certain aesthetic conditions external of the plumbing system may not be attained AquaSolve is designed for the treatment of potable water that meets the requirements of the current USEPA Safe Drin...

Page 5: ...applicable local codes Include sample drain ports with hose bibb connec tions on the inlet and outlet piping to facilitate startup and service Support the Piping 2 inch Flex Connectors must be installed horizontally not vertically in the water pipe line The full weight of the piping and valves must be supported by uni strut pipe hangers or other means The tank connections cannot support the weight...

Page 6: ...edia You need to take it out in small bites If you Your AquaSolve media should be replaced every 3 years Dispose of old media and or container in accordance with local regional national and or international regulations NOTICE let the whole pipe hose fill with media it will plug up You need to let slugs of water flush out the pipe as you go 11 When all the old media is removed turn off the garden h...

Page 7: ... media will be limited to furnishing a replacement for the media within two years from date of original installation Such replacement media will be delivered to the owner F O B nearest factory at no cost excluding freight and local labor charges if any Damage to the media due to chlorine other oxidizers or fouling caused by local water conditions or any other operation outside of the limits shown ...

Reviews: