Installation
Tighten the tank head
*It is very important to use flexible connections on the inlet and
outlet plumbing in the horizontal orientation as shown in the imag-
es on this page. The tanks expand and contract with water pres-
sure fluctuations. Flexible connectors will prevent plumbing and
tank leaks. The part number for the suggested Lync 2” Flexible
Connectors is 144065 (two are included and required for installa-
tion).
Anytime
AquaSolve
systems are installed above the ground floor
of a building it is recommended that a vacuum relief valve also be
installed to protect against tank collapse in the event the plumb-
ing system is drained. If a vacuum relief valve is not used then the
system should be placed in bypass anytime the plumbing system
is drained. The part number for suggested vacuum relief valve is
123318 (not included). The vacuum relief valve should be installed
on the outlet of the system.
NOTICE
• We recommend the installation of a dual-union ball-valve on
the inlet and outlet to isolate the tank for servicing.
• A full bypass should be installed so that the full service flow
can be routed around the system as needed for servicing.
NOTICE
Install Piping
Connect the inlet and outlet plumbing according to
your preferences and any applicable local codes.
Include sample/drain ports with hose-bibb connec-
tions on the inlet and outlet piping to facilitate startup
and service.
Support the Piping
2 inch Flex Connectors must be installed horizontally not vertically
in the water pipe line. The full weight of the piping and valves must
be supported by uni-strut, pipe hangers or other means. The tank
connections cannot support the weight of the piping. The image
below for a multi-tank system installation shows properly support-
ed piping.
WARNING
Start-Up
Connect a hose to the hose bibb on the outlet of
the tank. Run the hose to a drain and open the hose
bibb.
Slowly/partially open the supply water ball valve.
Allow the tank to slowly fill with water. When a
Fill in install date and rebed due date on product label located
on front of each tank as reminder to replace
AquaSolve
media
every 3 years. The system is now ready for operation.
NOTICE
Typical Installation for Single and
Multi-Bank Systems
steady stream of water appears at the drain, close
the supply valve and hose bibb. Once the tank is full,
wait 4 hours for media to “hydrate”.
Slowly open the inlet and outlet valves on the sys-
tem. Transfer the bypass valve from Bypass to the
Service position. Open a nearby faucet downstream
from the AquaSolve system to relieve any air.
Check for leaks. Repair as needed.
Check the head on top of the tank. It’s common for it to loosen
during shipment. Tighten the head with a strap wrench as needed.
NOTICE