Specifications

AquaSolve scale prevention system shall be installed 
on the main water service pipe just after it enters the 
building, but after other whole building water safety 
devices (backflow preventers or pressure reducing 
valves), to effectively address water hardness con-
cerns. A system may also be installed further down-
stream to protect specific equipment or areas within 
a plumbing system. The system shall be plumbed 
with a bypass valve to allow isolation of tank(s) and 
to allow the bypass of untreated water in the event 
that service or media replacement be necessary. The 
installation area should be suitable in size for the 
tank(s) to be serviced without encumbrance and sit 
upright on a flat level surface.

The system must operate in an upflow manner and 
does not require additional water to backwash, flush, 
or regenerate once put into service. The system does 
not require any chemical additives and does not 
require electricity for operation.

Multi-tank systems shall be installed in parallel  
with PVC/CPVC manifold to meet peak flow rate 
requirements – see image below.

Spotting May Occur on External Plumbing Surfaces.

  

AquaSolve media systems perform best in single pass pota-
ble water applications with NO additional chemical additives. 
Depending on hardness, soft scale spotting may occur. Soft scale 
spots in most cases can be easily wiped down with a damp cloth 
and will not form hard scale deposits. A Point of Use (POU) Water 
Softener should be used on mandatory spot-free applications (e.g. 
glass stemware, dishware).

NOTICE

Using AquaSolve With Other Water Treatment Equipment.

Due to the unique properties of AquaSolve, there are some unique 
requirements for using AquaSolve in conjunction with other forms 
of water treatment:

1. AquaSolve must be the last stage in the treatment chain. Do 

not install any filters after Lync AquaSolve or before any devic-
es for which scale prevention is required. POU filters, e.g. car-
bon, RO or Ultraviolet (UV) are exempt from this requirement.

2. Do not apply any other antiscalants before or after AquaSolve.

3. The addition of soaps, chemicals, or cleaners, before or after 

AquaSolve treatment, may reverse its anti-scale treatment 
effects and/or create water with a heavy residue or spotting 
potential. Any adverse conditions caused by the addition of 
soaps, chemicals, or cleaners are the sole responsibility of the 
end user.

4. AquaSolve is not a water softener and does not soften the 

water - water treatment chemistry (e.g. antiscalants, seque-
trants, soaps, chemicals or cleaners etc.) will most likely have 
to be changed to be compatible with Lync AquaSolve treat-
ed water. Laundry and ware-washing chemistry will likewise 
require adjustments.

WARNING

•  Not for use on closed loop systems.
•  Do not let the system freeze. Damage to the tank may result.
•  System must be operated in a vertical position. Do not lay 

it down during operation. The system may be placed in any 
position for shipping and installation but must be operated in 
the vertical position.

•  Place the system on a smooth, level surface. Because the sys-

tem operates in an upflow, fluidized bed mode, having a level 
surface is more important than with a softener or media filter.

•  A bypass valve should be installed on every system to facili-

tate installation and service.

•  Observe all local plumbing and building codes when installing 

the system.

CAUTION

Standards

Independent scientific testing has confirmed 
Template Assisted Crystallization (TAC) technology 
provides scale reduction of over 95+%. Testing was 
conducted under protocol based on DVGW W512 
test to access control of scale formation.

Operation & Maintenance Manual

Lync AquaSolve

L-OMM-010_A

Summary of Contents for Lync AquaSolve LM8414TM-COM

Page 1: ...00 Fort Worth TX 76134 817 335 9531 Technical Support 800 433 5654 ext 3 Mon Fri 8 am 5 pm CST Engineered Solutions L OMM 010_A Important Read this Manual BEFORE using this equipment Failure to read and follow all safety and use information can result in death serious personal injury property damage or damage to the equipment Keep this Manual for future reference 2021 Lync ...

Page 2: ...rystals making AquaSolve an effec tive alternative technology to a water softener for the prevention of scale due to water hardness Virtually maintenance free no control valve Uses environmentally friendly technology by using no salt or other chemicals to constantly add no electricity and no wastewater Improves efficiency of all water using appliances both hot and cold Simple sizing and installati...

Page 3: ...olve in conjunction with other forms of water treatment 1 AquaSolve must be the last stage in the treatment chain Do not install any filters after Lync AquaSolve or before any devic es for which scale prevention is required POU filters e g car bon RO or Ultraviolet UV are exempt from this requirement 2 Do not apply any other antiscalants before or after AquaSolve 3 The addition of soaps chemicals ...

Page 4: ...g AquaSolve technology prevent hard water scale formation inside the plumbing system at influent hardness levels of 30 grains per gallon of calcium carbonate and less Due to vari ances in water chemistry certain aesthetic conditions external of the plumbing system may not be attained AquaSolve is designed for the treatment of potable water that meets the requirements of the current USEPA Safe Drin...

Page 5: ...applicable local codes Include sample drain ports with hose bibb connec tions on the inlet and outlet piping to facilitate startup and service Support the Piping 2 inch Flex Connectors must be installed horizontally not vertically in the water pipe line The full weight of the piping and valves must be supported by uni strut pipe hangers or other means The tank connections cannot support the weight...

Page 6: ...edia You need to take it out in small bites If you Your AquaSolve media should be replaced every 3 years Dispose of old media and or container in accordance with local regional national and or international regulations NOTICE let the whole pipe hose fill with media it will plug up You need to let slugs of water flush out the pipe as you go 11 When all the old media is removed turn off the garden h...

Page 7: ... media will be limited to furnishing a replacement for the media within two years from date of original installation Such replacement media will be delivered to the owner F O B nearest factory at no cost excluding freight and local labor charges if any Damage to the media due to chlorine other oxidizers or fouling caused by local water conditions or any other operation outside of the limits shown ...

Reviews: