37
Powers
TM
IntelliStation BAS Integration Manual
The Intellistation is equipped with a 1069 Control Module designed and programed by tekmar Control Systems
Ltd. This control can communicate with a Building Automation System (BAS) using BACnet
®
IP, BACnet
®
MSTP,
or Modbus
®
. This manual provides information about the measurements, control parameters, and error mes-
saging which can be accessed by building automation and/or management systems that use BACnet
®
IP,
BACnet
®
MSTP, or Modbus
®
communication. The 1069 Control Module can be configured to provide remote
monitoring and remote temperature set-point control from the connected BAS. See IntelliStation User Guide &
Instruction Manual for additional information.
1. Configure the control to communicate using the “User Interface-BAS Menu” information within this
manual and/or the “BAS Integration Manual.”
1. After completely de-energizing and disconnecting all power from IntelliStation
®
and performing required
LOCK OUT/TAG OUT, carefully open the IntelliStation control module by releasing latches to reveal
BACnet
®
and Modbus
®
hook up terminals.
Configuring the Control for BAS communication
Introduction
BAS Connection Procedure
BEFORE attempting to connect BAS, a
certified and qualified electrician
MUST fully de-energize and disconnect
all electrical power from IntelliStation
®
.
Perform required LOCK OUT/TAG OUT
procedures.
BAS connection MUST be performed
by certified and qualified electrician.
DANGER
!