IM-HKM40-50_HK40-50-DE-W-UK-12-2019-Rev.1 | Part no. 10083684
3
EN
ENGLISH
2 Technical features
Hydraulic data
HKM40/HK40 and HKM50/HK50
Max. operating pressure
6 bar
Min. ambient temperature
-10 °C (note pump specification)
Max. ambient temperature
+40 °C (note pump specification)
Min. operating temperature
+2 °C (note pump specification)
Max. operating temperature
+90 °C (note pump specification)
Centre distance
180 mm
Gravity brake closing pressure
10 mbar
Temperature display range
0 - 120 °C
Media
Water or water with glycol as per VDI (Association of German Engineers) 2035 / ÖNORM
(Austrian standard) H 5195
Electrical connection
Power supply
See separate pump documentation
Dimensions
Width x height x depth with EPP shell
720 mm x 410 mm x 260 mm
Weight
DN40 / DN50
HKM 40/50 Magna3
HKM 40/50 Stratos PARA
HKM 40/50 without pump
HK 40/50 Magna3
HK 40/50 Stratos PARA
HK 40/50 without pump
33.1 kg / 34.5 kg
25.3 kg / 31.2 kg
16.7 kg / 17.7 kg
29.8 kg / 31.5 kg
22.7 kg / 28.4 kg
13.3 kg / 13.5 kg
Connections to pipe network
2” male thread, flat sealing (190 Nm)
Materials
Return pipes
Tubular steel ø 60 mm
Fittings
Brass CW617N
Seals
AFM34/2
Insulation
EPP
Gravity brake
POM, NBR, stainless steel
Plastics
impact-resistant and temperature-resistant
O-rings
EPDM
Tightening torques for screw fittings
1½“; 130 Nm
2”; 190 Nm
Circulation pump
Technical information on the circulation pumps can be found in the relevant pump documentation.
Actuator
Technical information on the actuators can be found in the relevant actuator documentation.
DN 40
DN 50