background image

IM-HKM40-50_HK40-50-DE-W-UK-12-2019-Rev.1 | Part no. 10083684

11

EN

ENGLISH

7.3  Removing the circulation pump

1.  Disconnect the power supply and secure against 

reconnection.

2.  Remove the pump unit front cover.
3.  Close the shut-off valves.
4.   Disconnect the circulation pump wiring.
5.  Undo the flange and remove the circulation pump.

Severe scalding from hot water!

•  Allow the pump unit to cool down before 

carrying out maintenance work.

•  Do not put hands into hot medium when 

draining the pump unit.

7.4  Installing the circulation pump

1.  Replace damaged or defective seals if necessary.
2.  Insert the circulation pump and tighten the flange (see 

“Technical features“ on page 3 for tightening torques).

3.  Connect the circulation pump wiring.
4.  Slowly open the ball valve using the lever.
5.  Slowly pressurise the pump unit and bleed the system if 

necessary.

6.  Check the seals on the pump unit are not leaking.
7.  Reconnect the power supply to the pump unit.
8.  Refit the front cover.

7.5  Removing the 3-way mixing valve (HKM 

only)

1.  Disconnect the power supply and secure against 

reconnection.

2.  Remove the pump unit front cover.
3.  Close the shut-off valves.
4.  Move the regulating insert (spindle) to centre position using 

the lever on the actuator.

5.  Remove the actuator.

 

9

Instructions for fitting/removing the actuator can be 
found in the relevant manufacturer’s manual.

6.  Loosen the bolts and remove the 3-way mixing valve.

7.6  Fitting the 3-way mixing valve (HKM only)

1.  Replace damaged or defective seals.
2.  Fit the 3-way mixing valve and tighten the bolts.
3.  Fit the actuator.
4.  Slowly open the ball valve using the lever.
5.  Reconnect the power supply to the pump unit.
6.  Refit the front cover.

Summary of Contents for HK40 Series

Page 1: ...HKM40 50 HK40 50 Series Pump units for distributing heating water in heating systems Installation and operating manual WattsWater de...

Page 2: ...facturer 12 9 Warranty 12 1 General information 1 1 Important notes about the Installation and Operating Manual The operator is responsible for ensuring adherence to the local laws and regulations e g...

Page 3: ...n Dimensions Width x height x depth with EPP shell 720 mm x 410 mm x 260 mm Weight DN40 DN50 HKM 40 50 Magna3 HKM 40 50 Stratos PARA HKM 40 50 without pump HK 40 50 Magna3 HK 40 50 Stratos PARA HK 40...

Page 4: ...dy to install The pump unit is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of specialist knowledge or experience 3 4 Foreseeable mis...

Page 5: ...ENGLISH 4 Construction HKM40 50 pump unit Compact design Thermometer on the ball valve 3 way mixing valve with actuator HK40 50 pump unit Compact design Thermometer on the ball valve Ball valve with...

Page 6: ...ke return 2 Ball valve supply 3 Circulation pump 4 Return inlet 5 Supply outlet 6 Return outlet 7 Supply inlet 8 3 way mixing valve 9 Actuator 10 Connecting pipe 4 2 HK40 50 1 Ball valve with gravity...

Page 7: ...e 1 screw fittings 130 Nm 2 screw fittings 190 Nm Requirements The fittings are preassembled at the factory however the tightness of the seal is to be checked before commissioning pressure test 5 2 St...

Page 8: ...parts must be carried out only by trained electricians Disconnect the power supply to the unit before carrying out any installation maintenance cleaning or repair work and secure it against reconnect...

Page 9: ...IM HKM40 50_HK40 50 DE W UK 12 2019 Rev 1 Part no 10083684 9 EN ENGLISH 6 Performance curve Pressure drop Flow rate with mixer with mixer Pressure drop for Pressure loss for Pressure drop Flow rate...

Page 10: ...Functional check Check the correct adjustment and operating and performance parameters Check for noisy operation Check with the user in the event of anomalies 3 Ball valves Check for correct operatio...

Page 11: ...open the ball valve using the lever 5 Slowly pressurise the pump unit and bleed the system if necessary 6 Check the seals on the pump unit are not leaking 7 Reconnect the power supply to the pump uni...

Page 12: ...the pump unit in the correct way or engage a specialist company to do this 3 Separate the subassemblies and components into recyclable materials and operating materials 4 Dispose of the subassemblies...

Reviews: