RECOMMENDED PRESSURES
& TEMPERATURES
MIXED OUTLET TEMPERATURE
Temperature Adjustment Range
Set during installation/commissioning | Factory set at 40°C
35 - 48°C
(+/- 2 ˚C)
INLET TEMPERATURES
Cold Supply
Minimum
5°C
Maximum
30°C^
Hot Supply
Minimum
55°C
Maximum
90°C
Hot to Mix Temperature Differential for
Stable Operation
Minimum
10°C
Cold to Mix Temperature Differential for
Stable Operation
Minimum
5°C
FLOW RATES
Minimum 2 L/min
(4 L/min recommended for optimum performance)
Maximum
15mm 38 L/min
(31L/min @200kPa pressure loss as per flow sizing graph)
20mm 45 L/min
(39L/min @200kPa pressure loss as per flow sizing graph)
DYNAMIC INLET PRESSURES
Hot & Cold Inlet Pressures
For optimum operation it is recommended that the
hot and cold water supply pressures be balanced
/- 10% for both static and dynamic pressures.
Minimum
20kPa
Maximum
500kPa
STATIC INLET PRESSURES
Hot & Cold Inlet Pressures
For testing purposes/ system commissioning
Maximum
1600kPa
^ Where cold inlet temperature may exceed recommended range due to seasonal
variation, a 5°C temperature differential between the inlet cold supply and outlet mixed
temperature setting must be maintained.
NOTE: Notwithstanding the above, compliance with the Plumbing Code of Australia
(PCA) and AS/NZS 3500 must be maintained.
INLET PRESSURE RATIO
H - PL = H
¹
C - PL = C
¹
H
¹
: C
¹
= Max 10:1
C
¹
: H
¹
= Max 10:1
H = Hot inlet pressure (dynamic)
C = Cold inlet pressure (dynamic)
PL = Pressure Loss