PRM

Pressure switch with
manual setting for heating
systems.

0402101    1/4”F

3

Part No.      Size          bar

Pressure switch Series PRM is a switch with normally
closed contact; when the pressure of the system exceeds
the set pressure, the contacts are opened, thus interrup-
ting the circuit. Closing of the contacts (resetting of the
pressure switch) should be performed manually by pres-
sing the reset button.

APPLICATION AND OPERATION

To adjust the cut-off pressure, turn adjusting nut (2). The
set value can be read on relative scale (1). To reactivate
the system after making the adjustment, wait for the
pressure to drop at least 0.4 bar below set pressure, then
press the reset button at the bottom of the pressure
switch.

ADJUSTMENT OF SET PRESSURE

Contact (b) - (c) is normally closed (it opens when the set
pressure is reached). Connection to earth is via terminal
(a). View of the terminal board from above after removing
the cover:

ELECTRICAL CONNECTIONS

Approved in conformity with Body R (June 1982 edition) issued by I.S.P.E.S.L. 
CE mark in  conformity with European Directives EEC 89/336, EEC 73/23.

APPROVALS

Overall dimensions (mm)

a

b

c

2

(a) earth terminals
(b) line terminals
(c) motor terminals

DESIGN FEATURES

Connection

1/4" F

Inner cable gland diameter

11.5 mm max. (for cables H07RN-F-3X1)

Lever mechanism

galvanized steel

Electrical contacts

brass faced with Ag-CdO

Diaphragm

NBR rubber with fabric core

Cover

high impact ABS

TECHNICAL CHARACTERISTICS

Contact load rating

16 (10) A at 250 V ~ 

Rated voltage

250 V ~

Pressure setting range

1 ÷ 5 bar

Factory setting

3 bar

Max. fluid temperature

90 °C

Degree of protection

IP 40

Summary of Contents for DOLOMIT IGD Series

Page 1: ...LIQUIDS Flow switches interrupt an electrical control circuit when the water circulation fails in the circuit for some abnormal condition e g stop ping of motor driven pumps They are operated thanks t...

Page 2: ...e cable cable colour Blue Brown Black allows float switch Series IGD to be used for emptying or filling depending on the electrical connections as described below Emptying Black Brown connection conta...

Page 3: ...act size although still retaining electrical and float characteristics such as to ensure perfect operation Product reliability is ensured thanks to the sound expe rience of WATTS Cazzaniga in the sect...

Page 4: ...keep a certain distance from sources of turbulence elbows valves etc recommended min distance is equal to 5 times the pipe diameter to keep a minimum distance of 55 mm between the pipework and the lo...

Page 5: ...istance is equal to 5 times the pipe diameter to keep a minimum distance of 55 mm between the pipework and the lower base of the appliance INSTALLATION The 1 2 contact is normally open closes when the...

Page 6: ...switch ADJUSTMENT OF SET PRESSURE Contact b c is normally closed it opens when the set pressure is reached Connection to earth is via terminal a View of the terminal board from above after removing t...

Page 7: ...SET PRESSURE Contact b c is normally closed it opens when the set pressure is reached Connection to earth is via terminal a View of the terminal board from above after removing the cover ELECTRICAL CO...

Page 8: ...es com e mail info wattscazzaniga it The descriptions and photographs contained in this product specification sheet are supplied by way of information only and are not binding WATTS CAZZANIGA reserves...

Reviews: