7. Replacement kits
7.1 Seal kits
7.2 Spring kits
PN16, PN25 and PN40 seal kits
DN
Watts code
mm
“
50
2”
166922
65
2 ½’’
202174
80
3”
162935
100
4’’
167069
125
5’’
166929
150
6’’
162947
200
8’’
166930
DN 50-100 Item N°
140,150,160,170,180,185,190,195
DN 125-200 Item N°
160,170,180,190,200,210,220,260
Composition
1 kit with 1 piece of each item
Spring kits (2 to 8 bar)
DN
Watts code
mm
“
50
2”
166921
65
2 ½’’
166923
80
3”
162928
100
4’’
162931
125
5’’
202166
150
6’’
0599075
200
8’’
202167
Spring kits (4 to 12 bar)
DN
Watts code
mm
“
50
2”
167028
65
2 ½’’
166924
80
3”
166926
100
4’’
166927
125
5’’
166928
150
6’’
167092
200
8’’
167103
6.3 Modifying the adjustment range by changing the spring kit
Maintenance and assembly instructions:
1- De-pressurise the system and then isolate the device from it (remove from system if necessary),
2- Fully release the spring (150) (turn the adjuster screw (110) anti-clockwise),
3- Remove the valve head fixing screws (270) and then the valve head (20),
4- Remove the spring and washers (150-50),
5- Fit the new spring, with new washers if necessary,
6- Refit in reverse order to removal,
7- Re-fill with water and adjust as per the instructions provided above.
When ordering the kits, quote the information shown on the metal identification plate on the valve housing.