The Solenoid On-Off ACV with Hydraulic Check Feature is de-
signed to open fully or close drip-tight as commanded by the 
3-Way Solenoid Pilot, and close drip-tight when downstream 
pressure becomes greater than upstream pressure. The Solenoid 
Pilot directs upstream pressure into and out of the cover chamber 
of the 3-way Accelerator Pilot. When the cover of the Accelerator 
Pilot is pressurized, the main valve cover chamber is vented down-
stream (dry drain) or to atmosphere (wet drain), causing the valve 
to open fully. When the cover of the Accelerator Pilot is de-pres-
surized, the main valve cover chamber is connected to upstream 
pressure, causing the valve to close drip tight. Valve opening and 
closing speeds are separately adjustable. Engaging the Solenoid 
Manual operator simulates power to the solenoid, manually con-
trolling the main valve. Disengaging the Solenoid Manual operator 
returns the valve to electrical on-off service. 

1

X

X

X

X

Y/FC

5

P/L

2

4

3

6

6

1.  Prior to installation, flush line to remove debris.

2.  Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures. A Position 

Indicator can be installed to provide visual indication of valve position and operation without disassembly.

3.  Install isolation valves upstream and downstream of the main valve.

4.  Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page. Avoid installing 

valves 6" and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are designed for horizon-
tal in-line installation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and guide wear may 
occur if valve is not installed according to factory recommendations. Consult factory for detailed engineering review prior to order-
ing if valve is to be installed other than horizontally in-line.

5.  If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit 

from damage. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean and 
replaced exactly as removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.

6.  Connect solenoid wiring leads to desired switching device, using safe, standard electrical practices.

7.  After installation, vent entrapped air from valve cover and pilot system by following instructions on Technical Bulletin.

Start-up of an automatic control valve requires that proper procedures be followed. Time must be allowed for the valve to react to 
adjustments and the system to stabilize. The objective is to bring the valve into service in a controlled manner to protect the system 
from damaging over-pressure.

If downstream pressure becomes greater than upstream pressure, downstream pressure is admitted to the main valve cover chamber, 
closing the valve and preventing reversal of flow. Normal On-Off operation resumes when upstream pressure exceeds downstream pres-
sure. 

Specify voltage and MAIN VALVE actuation (energize to open or close), and "wet" or "dry" drain PRIOR to ordering.

1 – Main Valve (905GD - Single Chamber)
2 – Model 22-1 Accelerator Control
3 – 3-Way Solenoid
4 – Adjustable Closing Speed
5 – Adjustable Opening Speed
6 – Check Valve
X – Isolation Cocks

Installation

930GD-01-19 (Globe) Solenoid (On-Off) Control Valve with 
Hydraulic Check Feature (6" and Larger)

2          IOM-A-ACV-930-01-19_630-01-19   2115 

EDP# 1917086 

© 2021 Watts

Summary of Contents for AMES 930GD-01-19

Page 1: ...g the Solenoid Control Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the info...

Page 2: ...ing up main valve stem vertical Slow operation or premature stem and guide wear may occur if valve is not installed according to factory recommendations Consult factory for detailed engineering review...

Page 3: ...lve does not include a bleed valve bleed air by loosen ing a fitting on the valve or a plug at the highest point of the valve assembly STEP 5 Pressure the line by opening the upstream isolation valve...

Page 4: ...ain valve checking that the main valve opens Step 8 Actuate either electrically or manually the solenoid to closed position to check that the main valve closes STEP 9 Closing Speed Needle Valve Adjust...

Page 5: ...cification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm or...

Page 6: ...valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembly corroded damaged Inspect stem assembly clean replace if necessary Blockage...

Page 7: ...e cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require the...

Page 8: ...h or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are threaded...

Page 9: ...in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrity...

Page 10: ...less Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 13 Seat Disc Buna N Nitrile 14 Spa...

Page 11: ...IOM A ACV 930 01 19_630 01 19 2115 EDP 1917086 2021 Watts 11 NOTES...

Page 12: ...sulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control...

Reviews: