background image

Standard Components

Operation

The Combination Pressure Reducing and Sustaining Automatic Control 
Valve (ACV) with Hydraulic Check Feature is designed to automati-
cally reduce a fluctuating higher upstream pressure to a constant lower 
downstream pressure regardless of varying flow rates, and will throttle 
to sustain a minimum upstream pressure. It is controlled by a normally 
open, pressure reducing pilot designed to: 1) Open (allowing fluid out 
of the main valve cover chamber) when downstream pressure is below 
the adjustable setpoint, and 2) Close (allowing fluid to fill the main valve 
cover chamber) when downstream pressure is above the adjustable set-
point. A decrease in downstream pressure causes the valve to modulate 
toward an open position, raising downstream pressure. An increase in 
downstream pressure causes the valve to modulate toward a closed 
position, lowering downstream pressure.

The normally closed sustaining pilot remains open when upstream pres-
sure is above the adjustable setpoint, and modulates toward a closed 
position if upstream pressure falls below the setpoint. As the sustaining 
pilot closes, fluid is directed into the main valve cover chamber, allow-
ing the valve to modulate toward a closed position, raising upstream 
pressure. Normal pressure reducing operation resumes when upstream 
pressure is above the sustaining pilot setpoint, and downstream pres-
sure is below the reducing pilot setpoint.

If downstream pressure becomes greater than upstream pressure, 
downstream pressure is admitted to the main valve cover chamber, 
closing the valve and preventing reversal of flow. Normal backpressure 
or sustaining operation resumes when upstream pressure exceeds 
downstream pressure.

1

X

X

X

X

Y/FC

P/L

2

4

3

AOS

5

4

CLOSES VALVE

OPENS VALVE

FLOW

1.  Prior to installation, flush line to remove debris.

2.  Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures. A Position Indicator 

can be installed to provide visual indication of valve position and operation without disassembly.

3.  Install isolation valves upstream and downstream of the main valve.

4.  Open the isolation ball valves in the control tubing if so equipped. Failure to open these will prevent the valve from functioning properly.

Note: 

If using butterfly valves, ensure valve disc does not contact the main valve.

5.  Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page.

6.  Avoid installing valves 6" and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are designed for 

horizontal in-line installation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and guide wear may 
occur if valve is not installed according to factory recommendations. Consult factory for detailed engineering review prior to ordering if 
valve is to be installed other than horizontally in-line.

7.  If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit from dam-

age. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean and replaced exactly as 
removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.

8.  After installation, vent entrapped air from valve cover and pilot system by following instructions on Technical Bulletin.

Start-up of an automatic control valve requires that proper procedures be followed. Time must be allowed for the valve to react to 
adjustments and the system to stabilize. The objective is to bring the valve into service in a controlled manner to protect the system 
from damaging over-pressure.

1 – Main Valve (905GD - Single Chamber) 

2 – Pressure Reducing Control 

3 – Pressure Sustaining Control 

4 – Check Valve

5 – Fixed Orifice

X – Isolation Cocks

Installation

912GD-01 (Globe) Pressure Reducing and Sustaining Control 
Valve with Hydraulic Check Feature

2          IOM-A-ACV-912-01_612-01   2115 

EDP# 1917032 

© 2021 Watts

Summary of Contents for Ames 612GD-01

Page 1: ...2 Setting the Pressure Reducing Control 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions...

Page 2: ...valve inlet and outlet pressures A Position Indicator can be installed to provide visual indication of valve position and operation without disassembly 3 Install isolation valves upstream and downstr...

Page 3: ...n the valve If your valve does not include a bleed valve bleed air by loosening a fitting on the valve or a plug at the highest point of the valve assembly See Figure 1 Step 3 Pressure the line openin...

Page 4: ...ry of pressure is slow upon increased downstream demand turn the adjustment screw OUT counterclockwise increasing the rate of opening IF recovery of downstream pressure is too quick as indicated in a...

Page 5: ...Relief Sustaining Control screw IN clockwise until the inlet pressure begins to increase or OUT counterclockwise to decrease stopping at the desired pressure See Figure 4 Step 4 Allow pressure to stab...

Page 6: ...specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm...

Page 7: ...ly by partially opening from full closed position Improperly configured opening speed control if equipped Adjust opening speed control to verify functionality adjust as required Standard setting for o...

Page 8: ...move cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require...

Page 9: ...rush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thread...

Page 10: ...ts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrit...

Page 11: ...el 9 Stem Washer ASTM A276 304 Stainless Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iro...

Page 12: ...resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no cont...

Reviews: