ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX B: EQUIPMENT MONITOR AND CONTROL POINT DEFINITIONS
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
60
of
140
Appendix B-2: AERCO Electronic Control System (ECS) Point Definitions
Point
Name
BAS
Modbus
Data
Address
GF-108, GF-
124, GF-114
Point Name
Reg.
Type
Modbus
Data
Address
(Hex/Dec.)
Units (Range)
Electric Valve (ECS) and SmartPlate
Cntl Output
Signal
30004
OP (Control Output
Signal)
Input
0x0003 / 3
% (0 to 100)
Setpoint
30006
w.SP (Setpoint)
Input
0x0005 / 5
°F (40 to 180)
RmSetpt
40027
Remote Input
Comms Access
parameter(Setpoint)
Holding
0x001A / 26
°F (40 to 180)
Outlet
Temp
30002
Top Value (Outlet
Temp)
Input
0x0001 / 1
°F (40 to 205)
FBk Sensor
Temp
30290
Li1 (Feedback
Sensor Temp)
Input
0x0121 / 289
°F (40 to 180)
Over Temp
Alarm
30075
AL 1 (Over Temp
Alarm)
Input
0x004A / 74
Bit 0 = Alarm 1 State (0 = Safe 1 = Alarm).
Bit 1 = Alarm 2 State (0 = Safe 1 = Alarm).
Bit 2 = Alarm 3 State (0 = Safe 1 = Alarm).
Bit 3 = Alarm 4 State (0 = Safe 1 = Alarm).
Bit 4 = Manual Mode (0 = Auto 1 = Manual).
Bit 5 = Sensor Break (0 = Good PV 1 =
Sensor Broken.
Bit 6 = Loop Break (0 = Good closed loop 1
= Open Loop).
Bit 7 = Heater Fail (0 = No Fault 1 = Load
fault detected).
Flow Rate
/Mixed
Temp
30291
Li2 (Flow)
Input
0x0122 / 290
GPM or
̊F (40 to 205)
Standalone SmartPlate EV Points:
Point
Name
BACnet
Address
Lon Name
Lon SNVT
Modbus
Reg Type
Modbus
Data
Address
Unit
Range
SmartPlate EV
DHW Out
AV: 1
nvoSPEVDhwOut_XXX
SNVT_count_inc
Input
1
°F (40 to 220)
Setpoint
AV: 2
nviSPEVSetpoint_XXX
SNVT_count_inc
Holding
2
°F (40 to 180)
Valve POS
AV: 4
nvoSPEVValvePOS_XXX
SNVT_count_inc
Input
4
% (0-100)
DHW Flow
AV: 364
nvoSPEVDhwFlow_XXX
SNVT_count_inc
Input
364
GPM (0-150)
BW Inlet T
AV: 370
nvoSPEVBWInlet_T_XXX
SNVT_count_inc
Input
370
°F (40 to 220)
DHW Inlet T
AV: 373
nvoSPEVDhwInlet_T_XXX
SNVT_count_inc
Input
373
°F (40 to 220)
DP
AV: 379
nvoSPEVDP_XXX
SNVT_count_inc
Input
379
PSI (0 to 100)
Alarm 1 Out
AV: 10249
nvoSPEVAlarm1Out_XXX
SNVT_count_f
Input
10249
Alarm 2 Out
AV: 10265
nvoSPEVAlarm2Out_XXX
SNVT_count_f
Input
10265
Alarm 3 Out
AV: 10281
nvoSPEVAlarm3Out_XXX
SNVT_count_f
Input
10281
Alarm 4 Out
AV: 10297
nvoSPEVAlarm4Out_XXX
SNVT_count_f
Input
10297
Alarm 5 Out
AV: 10313
nvoSPEVAlarm5Out_XXX
SNVT_count_f
Input
10313
Alarm 6 Out
AV: 10329
nvoSPEVAlarm6Out_XXX
SNVT_count_f
Input
10329