ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX B: EQUIPMENT MONITOR AND CONTROL POINT DEFINITIONS
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
59
of
140
Appendix B-1:
AERCO C-More & ACS/BMS II/BMS Point Definitions
Point Name
BAS Modbus
Data Address
GF-108, GF-
124, GF-114
Point Name
Reg.
Type
Modbus Data
Address
(Hex/Dec.)
Units (Range)
Net Blr 8 Status
30033
Net Boiler 8
Input
0x0020 / 32
Same As Above
Net Blr 9 Status
30034
Net Boiler 9
Input
0x0021 / 33
Same As Above
Net Blr 10 Status
30035
Net Boiler 10
Input
0x0022 / 34
Same As Above
Net Blr 11 Status
30036
Net Boiler 11
Input
0x0023 / 35
Same As Above
Net Blr 12 Status
30037
Net Boiler 12
Input
0x0024 / 36
Same As Above
Net Blr 13 Status
30038
Net Boiler 13
Input
0x0025 / 37
Same As Above
Net Blr 14 Status
30039
Net Boiler 14
Input
0x0026 / 38
Same As Above
Net Blr 15 Status
30040
Net Boiler 15
Input
0x0027 / 39
Same As Above
Net Blr 16 Status
30041
Net Boiler 16
Input
0x0028 / 40
Same As Above
Net Blr 17 Status
30042
Net Boiler 17
Input
0x0029 / 41
Same As Above
Net Blr 18 Status
30043
Net Boiler 18
Input
0x0030 / 42
Same As Above
Net Blr 19 Status
30044
Net Boiler 19
Input
0x0031 / 43
Same As Above
Net Blr 20 Status
30045
Net Boiler 20
Input
0x0032 / 44
Same As Above
Net Blr 21 Status
30046
Net Boiler 21
Input
0x0033 / 45
Same As Above
Net Blr 22 Status
30047
Net Boiler 22
Input
0x0034 / 46
Same As Above
Net Blr 23 Status
30048
Net Boiler 23
Input
0x0035 / 47
Same As Above
Net Blr 24 Status
30049
Net Boiler 24
Input
0x0036 / 48
Same As Above
Net Blr 25 Status
30050
Net Boiler 25
Input
0x0037 / 49
Same As Above
Net Blr 26 Status
30051
Net Boiler 26
Input
0x0038 / 50
Same As Above
Net Blr 27 Status
30052
Net Boiler 27
Input
0x0039 / 51
Same As Above
Net Blr 28 Status
30053
Net Boiler 28
Input
0x0040 / 52
Same As Above
Net Blr 29 Status
30054
Net Boiler 29
Input
0x0041 / 53
Same As Above
Net Blr 30 Status
30055
Net Boiler 30
Input
0x0042 / 54
Same As Above
Net Blr 31 Status
30056
Net Boiler 31
Input
0x0043 / 55
Same As Above
Net Blr 32 Status
30057
Net Boiler 32
Input
0x0044 / 56
Same As Above
Return Temp
30059
Return Sensor
Temp
Input
0x0045 / 58
°F (40 to 220)
Input Output Status
30058
I/O Status
Input
0x0039 / 57
Bit 0 = Aux Relay Status
Bit 1 = Fault Relay Status
Bit 2 = Sys Start Relay Status
Bit 3 = Not Used
Bit 4 = Setback Status
Bit 5 = Interlock 2 Status
Bit 6 = Interlock 1 Status
Bit 7 = Not Used