Innovation Hot Water Hot Water Boiler User Manual
- INTERNATIONAL
CHAPTER 3 – OPERATION
Page
42
of
174
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0120_0A
11/15/2016
Phone: 800-526-0288
GF-128-I
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
25
IGST Version
V2.00 or Lower
V2.02
0
26
IGN Timing Setting
4 Sec
7 Sec
-
--CAUTION -
* DO NOT CHANGE the Analog Output menu item from its Default
setting (Valve Position 0-10V).
3.7 TUNING MENU
The Tuning menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by factory-trained personnel.
A full description of each item appears in Table A-4 of Appendix A – Innovation Menu Item
Descriptions.
Table 3-5. Tuning Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
Prop Band
1°F (-17.2°C)
200°F (93.3°C)
30°F (-1.1°C)
2
Integral Gain
0.00
10.00
3.00
3
Derivative Time
0.00 min
2.00 min
0.20 min
4
Warmup Prop Band
1°F (-17.2°C)
120°F (48.9°C)
95 °F (35°C)
5
Warmup Int Gain
.00
2.00
0.50
6
Warmup PID timer
0 sec.
240 sec.
20 sec.
7
Min Load Adj (an offset)
-50°F (-27.5°C)
+50°F (27.5°C)
0°F (0°C)
8
Max Load Adj (an offset)
-50°F (-27.5°C)
+50°F (27.5°C)
0°F (0°C)
9
FFWD Temp
30°F (-1.1°C)
245°F (118.3°C)
Read Only Value
10 Outlet Feedback
Yes (On) or No (Off)
Yes (On)
11 Feedback Gain
0.01
1.00
0.10
Breakpoints
– shown only if the Heatr Bkpt Dsp option in the Calibration Menu is Enabled (see
section 3-8). The Breakpoint values correspond to a 130°F default setpoint
12
Breakpt at 100%
30°F (-1.1°C)
240°F (115.6°C)
85°F (29.4°C)
13
Breakpt at 90%
30°F (-1.1°C)
240°F (115.6°C)
86°F (30°C)
14
Breakpt at 80%
30°F (-1.1°C)
240°F (115.6°C)
87°F (30.5°C)
15
Breakpt at 70%
30°F (-1.1°C)
240°F (115.6°C)
88°F (31.1°C)
16
Breakpt at 60%
30°F (-1.1°C)
240°F (115.6°C)
89°F (31.7°C)
17
Breakpt at 50%
30°F (-1.1°C)
240°F (115.6°C)
90°F (32.2°C)
18
Breakpt at 40%
30°F (-1.1°C)
240°F (115.6°C)
94°F (34.4°C)