Table A-4:
TUNING MENU ITEM DESCRIPTIONS
See section 3-7 for a range of choices and the default values.
MENU LEVEL & OPTION
DESCRIPTION
23
FDback Start Pos
Start of Feedback Position
24
Fdback End Pos
End of Feedback Position
25
Max Feedback
Max Feedback
26
Fdback Value
Monitor Feedback Value
27
Temp Gov Enable
Enables or Disables the Temperature Governor function. The
Temperature Governor aggressively reduces the effective Fire
Rate as the Outlet Temperature approaches the High
Temperature Limit.
28
GOV Limit-5
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -5, the effective Fire Rate will be reduced
by the value entered in “GOV Limit -5”
29
GOV Limit-7
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -7, the effective Fire Rate will be reduced
by the value entered in “GOV Limit -7”
30
GOV Limit-10
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -10, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -10”
31
GOV Limit-12
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -12, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -12”
32
GOV Limit-15
When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -15, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -15”
33
PID Output
Calculated PID Output
34
P Output
Proportional Band Output
35
I Output
Integral Output
36
D Output
Derivative Output
37
Reset Defaults?
Allows Tuning Menu options to be reset to their Factory Default
values.
38
Value Debug
For Factory Personnel ONLY
39
Above 70 Fuel
For Factory Personnel ONLY
40
Below 70 Fuel
For Factory Personnel ONLY
NOTE:
Feedback Gain (Item 11) is only displayed when Heater Tuning Display is enabled by
factory authorized personnel.