NATURAL GAS Manual Combustion Calibration Instructions
TABLE 4-3c: NATURAL GAS Final Valve Positions: BMK1500/2000 Duel Fuel
Valve %
BMK1500 DF
BMK2000 DF
NOx
CO
O
2
%
70%
6.0% ± 0.2%
6.5% ± 0.2%
≤20 ppm
<100 ppm
50%
6.3% ± 0.2%
6.5% ± 0.2%
≤20 ppm
<100 ppm
40%
7.0% ± 0.2%
6.5% ± 0.2%
≤20 ppm
<50 ppm
30%
7.0% ± 0.2%
6.5% ± 0.2%
≤20 ppm
<50 ppm
16%
8.0% ± 0.2%
5.5% ± 0.2%
≤20 ppm
<50 ppm
TABLE 4-3d: NATURAL GAS Final Valve Positions: BMK2500
–
3000
BMK2500 Single and Duel Fuel
Single Fuel
Dual Fuel
NOx
CO
Valve %
O
2
%
Valve %
O
2
%
70%
5.9% ± 0.2%
70%
5.9% ± 0.2%
≤20 ppm
<100 ppm
50%
6.0% ± 0.2%
45%
6.2% ± 0.2%
≤20 ppm
<100 ppm
40%
6.3% ± 0.2%
30%
6.0% ± 0.2%
≤20 ppm
<50 ppm
30%
6.3% ± 0.2%
20%
5.8% ± 0.2%
≤20 ppm
<50 ppm
16%
6.0% ± 0.2%
16%
6.0% ± 0.2%
≤20 ppm
<50 ppm
BMK3000 Single and Duel Fuel
70%
5.1% ± 0.2%
85%
5.4% ± 0.2%
≤20 ppm
<100 ppm
50%
6.1% ± 0.2%
65%
5.5% ± 0.2%
≤20 ppm
<100 ppm
40%
5.0% ± 0.2%
45%
5.7% ± 0.2%
≤20 ppm
<50 ppm
30%
6.4% ± 0.2%
30%
5.6% ± 0.2%
≤20 ppm
<50 ppm
14%
6.4% ± 0.2%
14%
6.2% ± 0.2%
≤20 ppm
<50 ppm
TABLE 4-3e: NATURAL GAS Final Valve Positions: BMK4000
Valve Position
Standard NOx
Ultra-Low NOx
CO
Single Fuel
O
2
%
NOx
O
2
%
NOx
70%
5.5% ± 0.2%
≤20 ppm
6.0% ± 0.2%
≤9 ppm
<100 ppm
50%
5.5% ± 0.2%
≤20 ppm
6.0% ± 0.2%
≤9 ppm
<100 ppm
40%
5.5% ± 0.2%
≤20 ppm
6.0% ± 0.2%
≤9 ppm
<50 ppm
30%
5.5% ± 0.2%
≤20 ppm
6.0% ± 0.2%
≤9 ppm
<50 ppm
23%
6.0% ± 0.2%
≤20 ppm
6.5% ± 0.2%
≤9 ppm
<50 ppm
TABLE 4-3f: NATURAL GAS Final Valve Positions: 5000N
Valve Position
Standard NO
x
Ultra-Low NO
x
CO
O
2
%
NO
x
O
2
%
NO
x
70%
5.5% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<100 ppm
50%
5.5% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<100 ppm
40%
5.5% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<50 ppm
30%
5.5% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<50 ppm
18%
6.0% ± 0.2%
≤20 ppm
7.5% ± 0.2%
≤9 ppm
<50 ppm