BMK 5000N AERtrim Values
MENU ITEM
Minimum
Maximum
Default
Settle Time
0
120 sec
20 sec
Trim Gain
0.1
5.0
0.250
Max Tries
0
100
15
O
2
Target
(must be
between
O
2
Upper &
O
2
Lower)
18%
3
8
6.0
30%
3
8
5.5
40%
3
8
5.5
50%
3
8
5.5
70%
3
8
5.5
100%
3
8
5.5
O
2
Lower
(must be at
least 1%
lower than
O
2
Upper)
18%
2.5
5.5
5.5
30%
2.5
5.5
5.0
40%
2.5
5.5
5.0
50%
2.5
5.5
5.0
70%
2.5
5.5
5.0
100%
2.5
5.5
5.0
O
2
Upper
(must be at
least 1%
higher than
O
2
Lower)
18%
5.5
8.5
6.5
30%
5.5
8.5
6.0
40%
5.5
8.5
6.0
50%
5.5
8.5
6.0
70%
5.5
8.5
6.0
100%
5.5
8.5
6.0
O
2
Offset
-3.0
3.0
1.0
BMK5000N AERtrim Adjustment Range
CALIBRATION POINT
BLOWER VOLTAGE
Minimum
Maximum
Default
18%
1.00
2.00
1.32
30%
2.00
3.20
2.47
40%
2.90
5.20
3.70
50%
3.20
6.10
4.15
70%
3.80
7.20
4.70
100%
5.70
10.00
7.20