TROUBLESHOOTING
8
-4
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
(continued)
7. Defective Differential Pressure
Regulator
8. Carbon or other debris on Burner
7. Check gas pressure readings using gauge or manometer into
and out of the Air/Fuel Valve to ensure gas is getting to the
burner.
8. Remove the burner and inspect for any carbon or debris. Clean
and reinstall
FLAME LOSS
DURING RUN
1. Worn Flame Detector or cracked
ceramic.
2. Defective Differential Regulator.
3. Poor combustion calibration.
4. Debris on burner.
5. Blocked condensate drain.
1. Remove and inspect the Flame Detector for signs of wear or
cracked ceramic. Replace if necessary.
2. Check gas pressure readings using a gauge or manometer into
and out of the Air/Fuel Valve to ensure that the gas pressure
into and out of the valve is correct.
3. Check combustion calibration. Adjust as necessary.
4. Remove the burner and inspect for any carbon or debris. Clean
and reinstall.
5. Remove blockage in condensate drain.
HEAT DEMAND
FAILURE
1. The Heat Demand Relays on the
Ignition/Stepper board failed to
activate when commanded
2. Relay is activated when not in
Demand
1. Press CLEAR button and restart the unit. If the fault persists,
replace Ignition/Stepper (IGST) Board.
2. Defective relay. Replace IGST Board.
HIGH EXHAUST
TEMPERATURE
1. Defective exhaust sensor.
2. Carboned heat exchanger due to
incorrect combustion calibration
1. Measure the actual exhaust temperature and continuity of the
exhaust sensor. If the exhaust temperature is less than 475
o
F
and the exhaust sensor shows continuity replace the sensor.
2. If exhaust temperature is greater than 500
o
F, check
combustion calibration. Calibrate or repair as necessary.
HIGH GAS
PRESSURE
1. Incorrect supply gas pressure.
2. Defective SSOV Supply Regulator.
1. Check to ensure gas pressure at inlet of SSOV is 2 psig
maximum.
2. If gas supply pressure downstream of SSOV cannot be
lowered, to 4.8” W.C. (see para. 4.3, step 8), the SSOV Supply
Regulator may be defective. For Benchmark 2.0 Low NOx
boilers configured for De-Rated capacity (see para. 2.4.1), if
gas supply pressure downstream of the SSOV cannot be
lowered to
Summary of Contents for AERCO Benchmark 2.0LN
Page 9: ... This page intentionally blank ...
Page 19: ... This page intentionally blank ...
Page 29: ... This page intentionally blank ...
Page 35: ... This page intentionally blank ...
Page 41: ...5 1 This page intentionally blank ...
Page 47: ...SAFETY DEVICE TESTING 6 1 This page intentionally blank ...
Page 70: ...APPENDIX C C 1 Temperature Sensor Resistance Chart Balco ...
Page 77: ...APPENDIX F F 2 ...
Page 78: ...APPENDIX F F 3 ...
Page 79: ...APPENDIX F F 4 ...
Page 92: ...APPENDIX G G 5 ...